EDAM-4200 Series User’s manual Version 1.03
12.9
DO Auto-Off Time Mode
This function is used to force the specific DO channel to work as a monostable operation. After a certain period of
time, the DO returns to the stable state until another triggering command is applied.
♦
Low to High DO(n) pulse output
♦
♦
High to Low DO(n) pulse output
♦
ASCII command:
1.
$AACONNDD ;Set DO(n) to DO Auto-Off Time Mode
2.
$AA9DNNHHHHLLLL ;Set high /low delay width of DO(n)
3.
#AA1NDD ; Write DO channel to active
Example:
Set the channel-0 of DO to active and the channel-0 of D/O will be auto-off(inactive) after 3 sec.
1. $01CO0006 - Se to DO(0) Auto-Off Time Mode for DO "Low->High->Low.
(output low is active (ON), outputt high/open is inactive)
2. $019D0017700001 - Set DO High delay time(HHHH=3000ms) and Low delay time(LLLL= 0.5ms).
(For " Low->High->Low Auto-Off Time mode" LLLL always "0001")
3. #011001 - Write DO channel(0) to active
wait DO auto-off time (3sec)…….....,
...
4. the DO channel(0) auto-off from active to inactive.
Example:
Set the channel-1 of DO to inactive and the channel-1 of D/O will be auto-off(active) after 3 sec.
1. $01CO0107 - Se to DO(1) Auto-Off Time Mode for DO "High->Low->High.
(output low is active (ON), outputt high/open is inactive)
2. $019D0100011770 - Set DO High delay time(HHHH=0.5ms) and Low delay time(LLLL= 3000ms).
(For " High->Low->High Auto-Off Time mode" HHHH always "0001")
3. #011100 - Write DO channel(1) to inactive
wait DO auto-off time (3sec)…….....,
...
4. the DO channel(1) auto-off from inactive to active.
♦
Modbus rtu command:
1. X+1453 ~ X+1484 ;Set DO(0~31) to low to high delay mode(=2) or high to low delay mode(=3)
2. X+1711 ~ X+1774 ;Set high/low delay time of the specific DO(n)
3. X+1775 ~ X+1806 ;Start
auto-off time Mode
operation
Printed Date: 27 February 2018