12.1
INIT* switch operation
The EDAM-4200 “INIT*mode” has two purposes, one for reading module current configuration, and another for
configuring the module
IP Address, Subnet Mask, and Gateway
.
♦
Reading module current configuration
Each EDAM module has a built-in EEPROM which is used to store the configuration information such as address
ID, type, DIO mode etc.. If the user unfurtunally forget the configuration of the module. User may use a special
mode called “INIT* mode” to resolve the problem When the module is set to “INIT* mode”, the default settings
are IP Address, Subnet Mask, and Default Gateway
(10.0.0.1, 255.255.255.0 and 10.0.0.1)
♦
Originally, the INIT mode is accessed by connecting the INIT* terminal to the GND terminal. New EDAM-4200
modules have the INIT switch located on the rear side of the module to allow easier access to the INIT mode.
For these modules, INIT mode is accessed by sliding the INIT switch to the Init position as shown below.
♦
The following steps show you how to enable INIT* mode and read the current configuration:
1.
Power off the module.
2.
Sliding the INIT switch to the “Init” position.
3.
Power on the module.
4.
Start up the Windows Utility, it will search all EDAM-4200 I/O modules on the host PC’ to read the current
configuration stored in the EEPROM and set new
IP Address, Subnet Mask, and Default Gateway
,
5.
Power off the module again
6.
Sliding the INIT switch to the “Normal” position.
♦
Factory default settings:
1.
IP Address
: 10.0.0.1
2.
Subnet Mask : 255.255.255.0
3.
Gateway
: 10.0.0.1
4.
DHCP
: Disabled
5.
Web Server : Disabled
6.
Module ID
: 01
7.
Password
: 00000000