21
return to normal display and control. Or press any button to
turn the buzzer alarm off only.
4.3 Compressor Delay Time
(
PT
)
In the cooling mode, when the power is turned on for the first
time, PV(measured temperature value) ≥ TS(Temperature
setting value) + CD(Cooling difference value), it will not start
cooling immediately, but waiting for a delay time(PT).
When two adjacent of cooling starting intervals are greater
than the delay time, it will immediately start cooling; When two
adjacent of cooling starting intervals are less than the delay
time, it needs to operate the remaining delay time to start the
cooling.
Delay time will start counting from the cooling output off.
4.4 Temperature Calibration
(
CA
)
When the measured temperature deviates from the standard
temperature, the temperature calibration function can be used
to make the measured value of the instrument consistent with
the standard value. The calibrated temperature=the measured
tempe the calibration value.
4.5 Fahrenheit or Celsius Settings
(
CF
)
The users can set the display unit to Fahrenheit or Celsius
according to their habits. The default temperature is
Fahrenheit. If you need to display the unit in Celsius, then set
the CF to C. Please note that when the CF changes state, all
setting values are restored to the default setting and the
buzzer gives a short beeping prompt.
4.6 Time-Temperature Setting Values Execution Cycle
Times MD and Time-Temperature Parameter Settings
(
TR,UT,STT,SST,S01~S12,H01~H12,U01~U12
)
4.6.1 MD
is the execution times of the time-temperature
setting value. From the SST setting value to the last stage
setting value of STT, it is a cycle. If MD=0 represents an
infinite loop, MD=1~999 represents the specific times of cycle
execution. The default value of MD is 1. Under the condition of
MD=1~999, after the corresponding execution cycles is
Summary of Contents for ITC-608T
Page 1: ...ITC 608T Manual...
Page 7: ...5 86 8f 96 0f WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller...
Page 15: ...13 86 8f 96 0f WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller...
Page 28: ...26 DUAL TEMPERATURE PROBES Controller Manual ITC 608T Part 4...
Page 29: ...27 WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller 88 6f 98 6f...
Page 38: ...36 HUMIDITY Controller Manual Equivalent to IHC 200 Humidity Controller Manual ITC 608T Part 5...
Page 39: ...37 56 8 66 0 WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller...
Page 46: ...44 WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller 88 6f 56 8...