Installation Manual
Ingecon® Sun Three-Phase Inverter
Pg. 35 de 40
Ref.: AAS2000IKI02
Rev.:_ Dec-2009
8.2
List of alarms and shutdown reasons
The following table shows the reasons that can be in relation with each alarm:
ALARM
SHUTDOWN REASON DESCRIPCTION
0x0000
No shutdown
No alarm, the inverter will start up if it has enough power
0x0001
FREC_ALARM
SR_FREC
Grid Frequency out of range
0x0002
VAC_ALARM
SR_VAC
Grid Voltage out of range
0x0004
CURR_PI_SAT_ALARM
SR_CURR_PI_SAT
Red current is much more lower than the target current in that phase
0x0008
RESET_ALARM
SR_WD_RESET
Firmware fault.
0x0010
CURRENT_RMS_ALARM
SR_CURRENT_RMS
RMS current value exceeds maximun alowed value
0x0020
TEMPERATURE_ALARM
SR_TEMPERATURE
Electronics temperature exceeds 80ºC.
SR_AUX.TEMP
Temperature auxiliar sensor has detected an alarma
0x0040
ADC_ALARM
SR_ADC_READING
Error in Analog-to-Digital Converter
SR_ADC_LAT
Internal Error of the Analog-to-Digital Converter
0x0080
CURR.PEAK_ALARM
SR_CURR.PEAK
Instantaneus current value out of range
0x0100
PROT_CA_ALARM
SR_VARISTORS
Error at AC varistors of AAS0043
SR_CONTACTOR
Status of contactor incoherent with the status of the inverter.
SR_AC_PROT
Error at AC protections, dischargers, fuses...
SR_AC_MAG_PROT
Error at three-phase input breaker (60 to 100 kW inverters)
0x0200
PROT_DC_ALARM
SR_PARO_FUS_DC
DC input fuses fused, or DC dischargers
0x0400
VARISTORS_ALARM
SR_VARISTORS
Error en los varistores de DC
0x0800
FAULT_ALARM
SR_FAULT(1)
Line 1 power electronics Fault
SR_FAULT(2)
Line 2 power electronics Fault
SR_FAULT(3)
Line 3 power electronics Fault
0x1000
MANUAL_STOP_ALARM
SR_MANUAL_STOP
Manual Stop by Emergency Mushroom, display or comunication.
0x2000
CONFIG_ALARM
SR_CONFIG
Stop by a Firmware modification
SR_FIRMWARE.CH
Stop by a Firmware upload
0x4000
VDC_ALARM
SR_VDC
High voltage at DC input.
0x8000
MIN_VPV_ALARM
SR_MIN_VPV
Stop because of low voltage. As the inverter controls this voltage, it
should never happen.