Microprocessor Controller
93
34
Ambient Air Sensor Open Circuit
(Check Alarm)
• Sensor circuit resistance is higher than 100,000
ohms.
• Temperature is below -70 C (-94 F).
• Indicates:
• Open circuit to sensor
• Defective or wrong sensor
• Defective relay board
• Defective cable No. 1
• Defective controller
• Check sensor resistance between pins 13 and
14 on plug J15. Resistance must be 1,000
ohms at 25 C (77 F).
• Check cable No. 1 between controller and relay
board.
35
Ambient Air Sensor Short Circuit
(Check Alarm)
• Sensor circuit resistance is lower than 200
ohms.
• Temperature is above 80 C (176 F).
• Indicates:
• Short circuit to sensor
• Defective or wrong sensor
• Defective relay board
• Defective cable No. 1
• Defective controller
• Check sensor resistance between pins 13 and
14 on plug J15. Resistance must be 1,000
ohms at 25 C (77 F).
• Check cable No. 1 between controller and relay
board.
43
Return Air Temperature Too High
(Check Alarm)
• Return air temperature increases above 35 C
(95 F) during defrost.
• Indicates:
• Defective return air or evaporator coil sensor
• Return air and evaporator coil sensor
connections are reversed
• Check for sensor alarm codes.
• Check supply and return sensor connections
and locations.
52
• Probe Error
(Check Alarm)
• Occurs during Pretrip (PTI) test only.
• Temperature difference between supply air,•
return air or evaporator coil sensor is too high (3
C maximum)
• Indicates:
• Indication error on one of the sensors
• Supply air sensor not placed in airflow stream
• Check sensor connections. Check sensor
resistance of each sensor. Resistance must be
1,000 ohms at 25 C (77 F).
• Check supply air sensor locations.
Code
Description
Corrective Action
Summary of Contents for Thermo King CRR DF MPC2000
Page 5: ...4 ...
Page 11: ...List of Figures 10 ...
Page 13: ...Introduction 12 ...
Page 19: ...Safety Precautions 18 ...
Page 21: ...Service Guide 20 ...
Page 47: ...Unit Description 46 ...
Page 97: ...Microprocessor Controller 96 ...
Page 101: ...Electrical Maintenance 100 ...
Page 141: ...Structural Accessory Maintenance 140 ...
Page 147: ...Refrigeration System Diagnosis 146 ...
Page 150: ...149 CRR DF MPC2000 Controller Diagram ...
Page 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Page 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Page 153: ...152 CRR DF MP3000A Controller Diagram ...
Page 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Page 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Page 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Page 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Page 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...