Microprocessor Controller
61
•
Datalogger Menu: Menu screens in this group display temperature log, event log, set log time and
PTI log.
•
RMM (Remote Monitoring) State: Menu screen show current remote monitoring state (Offline,
Zombie or Online).
General Theory of Operation
The MPC2000 and MPC2000ID controllers use advanced solid-state integrated circuits to monitor and
control unit functions. The controller monitors inputs from:
•
Return air sensor
•
Supply air sensor
•
Evaporator coil sensor
•
Ambient sensor
•
USDA (Spare) sensors 1, 2 and 3
•
R-134a compressor discharge line temperature sensor
•
R-23 compressor discharge line temperature sensor
•
Phase measuring circuits
•
Current measuring circuits
•
Voltage measuring circuits
Output signals from the controller automatically regulate all unit functions including:
•
Compressor operation
•
Condenser fan operation
•
Evaporator fan motor operation
•
Liquid line solenoid valve
•
Electric heaters
•
Phase selection
Frozen Loads (Setpoint at -10 C [14 F] and Below)
NOTE: CRR DF units are designed to haul deep frozen cargo only at setpoints between -10 C (14 F)
and -60 C (-76 F).
At setpoints of -10 C (14 F) and below, the microprocessor controls unit operation based on the return air
sensor temperature and setpoint temperature.
The system operates on Full Cool to provide accurate control of frozen cargo. If the return air sensor
becomes disconnected or fails while it is being used to control unit operation, the controller will
automatically operate the unit continuously on Full Cool.
Summary of Contents for Thermo King CRR DF MPC2000
Page 5: ...4 ...
Page 11: ...List of Figures 10 ...
Page 13: ...Introduction 12 ...
Page 19: ...Safety Precautions 18 ...
Page 21: ...Service Guide 20 ...
Page 47: ...Unit Description 46 ...
Page 97: ...Microprocessor Controller 96 ...
Page 101: ...Electrical Maintenance 100 ...
Page 141: ...Structural Accessory Maintenance 140 ...
Page 147: ...Refrigeration System Diagnosis 146 ...
Page 150: ...149 CRR DF MPC2000 Controller Diagram ...
Page 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Page 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Page 153: ...152 CRR DF MP3000A Controller Diagram ...
Page 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Page 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Page 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Page 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Page 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...