Microprocessor Controller
88
03
Return Air Sensor Short Circuit
(Check Alarm)
• Sensor circuit resistance lower than 200 ohms.
• Temperature above 80 C (176 F).
• Indicates:
• Open circuit to sensor
• Defective or wrong sensor
• Defective relay board
• Defective cable No. 1
• Defective controller
• Check sensor resistance between pins 3 and 4
on plug J15. Resistance must be 1000 ohms at
25 C (77 F).
• Check cable No. 1 between controller and relay
board.
04
Evaporator Coil Sensor Open Circuit
(Check Alarm)
• Sensor circuit resistance higher than 100,000
ohms.
• Temperature below -80 C (-112 F).
• Indicates:
• Open circuit to sensor
• Defective or wrong sensor
• Defective relay board
• Defective cable No. 1
• Defective controller
• Low evaporator coil temperature
• Check sensor resistance between pins 5 and 6
on plug J15. Resistance must be 1,000 ohms at
25 C (77 F).
• Check cable No. 1 between controller and relay
board.
• Check evaporator airflow.
05
Evaporator Coil Sensor Short Circuit
(Check Alarm)
• Sensor circuit resistance lower than 200 ohms.
• Temperature above 80 C (176 F).
• Indicates:
• Open circuit to sensor
• Defective or wrong sensor
• Defective relay board
• Defective cable No. 1
• Defective controller
• Check sensor resistance between pins 5 and 6
on plug J15. Resistance must be 1,000 ohms at
25 C (77 F).
• Check cable No. 1 between controller and relay.
06*
R-134 Compressor Current Too High
(Check Alarm)
• Occurs during Pretrip (PTI) only.
• Compressor power consumption is higher than
approximately 13 amps.
• Indicates:
• Defective compressor or valve plate
• Defective volt or amp meter on relay board
• Inaccurate ambient temperature
measurement
• Out of range power supply
• Start “Manual Function Test”. Make sure the
compressor and condenser fan are operating.
Check compressor volts and amps.
• Check power supply volts.
• Check ambient sensor.
Code
Description
Corrective Action
Summary of Contents for Thermo King CRR DF MPC2000
Page 5: ...4 ...
Page 11: ...List of Figures 10 ...
Page 13: ...Introduction 12 ...
Page 19: ...Safety Precautions 18 ...
Page 21: ...Service Guide 20 ...
Page 47: ...Unit Description 46 ...
Page 97: ...Microprocessor Controller 96 ...
Page 101: ...Electrical Maintenance 100 ...
Page 141: ...Structural Accessory Maintenance 140 ...
Page 147: ...Refrigeration System Diagnosis 146 ...
Page 150: ...149 CRR DF MPC2000 Controller Diagram ...
Page 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Page 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Page 153: ...152 CRR DF MP3000A Controller Diagram ...
Page 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Page 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Page 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Page 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Page 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...