Microprocessor Controller
86
MPC 2000 ID / MP 3000, Super Freezer "Error message list"
#
Error Message
Controller Action
1
Power Error, Check 20A Fuses
Indicates:
• One or more phases are missing
• Compressor is able to draw amps on all
phases while heater lacks amps on one or
more phases
• Controller activates alarm 18
• Controller will try to restart unit after 60
minutes.
10
Cond probe found, please change type
Indicates:
• Controller is set for CRR40 DF and start-up is
initiated on a KVQ/CRR PS, CSR PS or CSR
Magnum unit. Correct by turning Un it On/Off
switch Off. Then set controller software switch
to correct position. See controller software
selection.
• None. On CRR40 DF units, condenser
sensor input must be left open.
11
Scroll Compressor, High Temperature
Indicates:
• Compressor stops because discharge
temperature is above 140 c (284 F). Message
remains in display until discharge temperature
decreases to normal.
• Controller clears message after
compressor start up.
12
Scroll Compressor, Low Pressure
Indicates:
• Low pressure cutout switch is open.
• Possible causes include stepper motor valve
will not open, warm gas bypass valve wil not
open, low refrigeratn charge, defective low
pressure cutout switch, open circuit, etc.
• Controller activates Alarm 31 after 5
minutes.
• Controller clears message after
compressor start up.
13
R134a Compressor, High Temperature
Indicates:
• Compressor stops because discharge
temperature is above 130 C (266 F).
Compressor remains Off until discharge
temperature decreases to 90 C (194 F)
• Controller actrivates Alarm 56.
• Controller clears message when
compressor temperature decreases below
130 C (266 F). However, compressor
remains off until discharge temperature
decreases to 90 C (194 F).
14
Evaporator High Temperature Switch Open
Indicates:
• Controller disables electric heaters due to
open high temperature switch circuit.
• Possible causes include evaporator
temperature over 54 C (130 F), defective
heater, defective evaporator overheat switch,
open circuit, etc.
• Controller clears message when high
temperature switch closes.
• NO alarm is set until Controller determines
that heater current draw is too high (alarm
10), unit current draw is too high (alarm
36), or defrost time is too long (alarm 20).
15
R134a Compressor Fault
• Feedback from 134a Compressor is Missing
• Check to be certain 134a compressor is
running
• Check continuity through 134a auxiliary
contactor on Main Relay Board plug J12.
Summary of Contents for Thermo King CRR DF MPC2000
Page 5: ...4 ...
Page 11: ...List of Figures 10 ...
Page 13: ...Introduction 12 ...
Page 19: ...Safety Precautions 18 ...
Page 21: ...Service Guide 20 ...
Page 47: ...Unit Description 46 ...
Page 97: ...Microprocessor Controller 96 ...
Page 101: ...Electrical Maintenance 100 ...
Page 141: ...Structural Accessory Maintenance 140 ...
Page 147: ...Refrigeration System Diagnosis 146 ...
Page 150: ...149 CRR DF MPC2000 Controller Diagram ...
Page 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Page 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Page 153: ...152 CRR DF MP3000A Controller Diagram ...
Page 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Page 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Page 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Page 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Page 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...