46
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - [email protected] – 03 11 AA AA 201 18
8.3
Safety Instructions
8.3.1
TO PROVIDE FOR.
• These “Safety Instructions” are associated with the “Operating Manual” regarding the equipment you have
purchased. Before proceeding with the installation or start-up, check that you have both sets of information, if
not, ask for them. Compliance with the “Safety Instructions” is compulsory and is the user’s legal responsibility.
Read them carefully, follow the steps in the given order and keep them for future reference. The local electrical
standards and different restrictions of the end user’s city may invalidate some of the recommendations given in
the manuals. In case of discrepancies, the user must comply with the pertinent local standards. The situation
may arise where the equipment’s distribution of connecting terminals and/or commands do not line up with the
manual’s illustrations. However, the simplicity of the operation together with the correct labelling provides for
easy understanding in an intuitive way.
• It is strictly forbidden to reproduce or to release this information without written permission from our
company.
• Do not install the machine in a corrosive or dusty atmosphere, and never outdoors.
• Do not obstruct the ventilation grates nor introduce objects through these or other orifices. Leave a minimum
free space of 25 cm around the machine for ventilation and air circulation.
• The location must be spacious, airy, away from heat sources and easily accessible. In addition to the
ventilation space indicated above, there must be an area of 75 cm clearance all round the device for possible
action by the After Sales Service (A.S.S.), so that if this involves moving the machine the connecting cables will
have the required space.
• Do not place materials on top of the machine or objects which would obstruct a proper view of readings.
8.3.2
GENERAL SAFETY INSTRUCTIONS.
• All equipment connections including those of the control should be done without the presence of the mains
supply and with the switches turned off, position “On”, “Off”, or respectively.
• Special attention should be paid to the labelling on the equipment warning about the “Risk of electric shock”
and indicators like (
). Hazardous live parts inside the equipment, do not remove the cover. Servicing is
reserved for qualified service personnel. For maintenance or repair services, contact your nearest After Sales
Service (A.S.S.) in our company.
• It is compulsory to connect the earth protection. Make sure that this is done before powering up the input to
the equipment.
For small equipment (input power cord provided with plug), the user should make sure that the wall outlet’s
voltage corresponds to the type delivered, properly grounded and connected to the local protection earth. For
equipment fitted with terminals, the licensed wirer should connect the earth wire to the terminal identified as
(
).
• The installation of hard wired equipment should be done by personnel qualified in electrical low voltage
installations.
• The cross section of the power supply and output cables to the loads should be determined according to the
rated current given on the equipment’s specifications plate and comply with the Local Low Voltage Electro
technical Regulations.
• The power supply cables to the equipment as well as to the loads, interfaces, etc. should be fastened to non-
movable parts to prevent pulling.
• Please keep in mind that if the equipment incorporates a Bypass with mains power available it will supply
output voltage even if the equipment is not turned on. Place warning notices and /or emergency switches as
requested by the safety Regulations of your specific installation.