(*) DSP Internal Error may occur for the following reasons:
Watch Dog failure.
Wrong ADC measures.
Communication errors between DSP and processor.
6.3.6
‘‘DATA LOGGER’’ level (screen menu 5.0).
Fig.28.
Screen 5.0 “Data logger” and its submenus.
Press key (
ESC
) on any screen of any submenu to return to main screen (
Screen 0.0
).
Screen 5.1:
Indicates the inverter runtime from the first unit start-up. This counter accumulates the total
inverter running time from the beginning and it is not possible to reset it.
Screen 5.2:
This screen indicates that the data logger is empty. This only happens if authorised personnel
reset this file. If the buffer is not empty, the following screen will inform of the data logger registers.
You can move through the different registers of this log file using the
(
) (
)
keys. The data logger file can
save up to 100 log registers.
You can see the three different screens per register, using the
(
) (
) keys,
with the information described
below.
Screen 5.3:
The same information appears in this screen as described above in the alarm screens except the
first three characters where there is a register counter from 00) to 99).
Screen 5.4:
This screen is divided into two rows.
In the first row there is information about alarm activation time and date:
hh: hour of alarm activation
mm: minutes of alarm activation
ss: seconds of alarm activation
mm: month of alarm activation dd: day of alarm activation
yy: year of alarm activation
In the second row there is information about deleted alarm time and date.
hh: hour of deleted alarm
mm: minutes of deleted alarm
ss: seconds of deleted alarm
dd: day of deleted alarm
mm: month of deleted alarm
yy: year of deleted alarm
(
)
(
)
˙˙˙
(
) (
)
01) UPS ON BYPASS
INITIALISE THE UPS
˙˙˙
˙˙˙
(
)
(
)
Screen 5.0
DATA LOGGER
(
)
(
)
Screen 5.1
HOURS INVERTER ON
145
(
)
(
)
Screen 5.4
ON: 09:27:35 - 05/10/09
OF: 09:43:20 - 05/10/09
Screen 5.3
00) INVERTER
OVERLOAD
(
)
(
)
(
)
(
)
(
)
(
)
R: RUN I: RUN P: INIT
U: UPS RUN FLGS:04
Screen 5.5
(
)
(
)