9.11. Ambient temperature high Alarm
It is shown “Ambient temperature high” on Alarm List. If the ambient temperature is high, it causes
a rise in
the internal temperature
of UPS and this alarm appears. In this case; the first thing to do is
cool down the environment.
9.12. Overload Alarms
Connected loads to the output of the UPS that exceed the nominal power of the unit is called
“Rectifier overload” and/or “Inverter overload”. Check if there is an overload and remove the
excessive load. Hence the alarm would be off.
UPS can supply
the load that exceeds the nominal power of the unit for a limited period while
operating in Online Mode. This period depends on the load % and the initial temperature of the
overload on the semiconductors.
The Unit follows up the following procedure in the calculation of the overload time:
It supplies
the load for a period which is specified in
Appendix-3 Technical Specifications
, and then
it transfers the load to bypass line if the bypass input voltage/frequency value is within the
allowed limits.
Meanwhile if the junction temperature passes over a certain value, than it transfers the load to
bypass line (assuming the bypass voltage/frequency is acceptable).
9.13. Manual bypass active Alarm
If Manual Mypass circuit breaker is brought to “I” position, this alarm appears. If Manual Bypass
circuit breaker is brought to “I” position without any reason (except the reasons explained in
), switch this circuit breaker to “0” position to remove the alarm.
9.14. Battery test failure Alarm
UPS tests the batteries periodically. In case the batteries failed in the battery test, this alarm appears.
Perform the test again when the batteries have been charged for min. 10 hours and verify the battery
circuit breaker is at "I" position.
If the alarm continues, contact to authorized Technical Service.
If the unit is working on bypass mode during the initial start of the overload or if it
has passed
to bypass mode because of the overload, then the only protection in the system is
the
automatic circuit breakers in the circuit. In case of the UPS circuit breaker is switched
off
then all the loads on the output would be deenergized.
Make sure that the UPS is not overloaded to provide a higher quality supply to the
loads.
Summary of Contents for ETR EVO Series
Page 16: ...ETR EVO UPS User Manual Ver 1 0 Page 11 10 15kVA 3Ph Input 3Ph Output Terminal Connections...
Page 17: ...ETR EVO UPS User Manual Ver 1 0 Page 12 20 30kVA 3Ph Input 3Ph Output Terminal Connections...
Page 18: ...ETR EVO UPS User Manual Ver 1 0 Page 13 40 60kVA 3Ph Input 3Ph Output Terminal Connections...
Page 19: ...ETR EVO UPS User Manual Ver 1 0 Page 14 80kVA 3Ph Input 3Ph Output Terminal Connections...
Page 20: ...ETR EVO UPS User Manual Ver 1 0 Page 15 100kVA 3Ph Input 3Ph Output Terminal Connections...
Page 21: ...ETR EVO UPS User Manual Ver 1 0 Page 16 120kVA 3Ph Input 3Ph Output Terminal Connections...
Page 22: ...ETR EVO UPS User Manual Ver 1 0 Page 17 160kVA 3Ph Input 3Ph Output Terminal Connections...
Page 23: ...ETR EVO UPS User Manual Ver 1 0 Page 18 200kVA 3Ph Input 3Ph Output Terminal Connections...
Page 36: ...ETR EVO UPS User Manual Ver 1 0 Page 31...
Page 71: ...ETR EVO UPS User Manual Ver 1 0 Page 66 40 200kVA Standard UPS 40 200kVA UPS with Split Bypass...