ETR EVO UPS User Manual (Ver. 1.0)
Page 29
5.1. Bypass Operation (Eco-Mode)
In this mode, as long as the mains voltage and frequency within the limits, the load is supplied by the
mains in a controlled manner (the inverter is in standby state). The purpose of using this mode is to
increase the efficiency up to 98,5% and to provide energy saving; since the loads are supplied by the
mains directly, the loads are unprotected against any possible future risks. (e.g. surge voltage, etc.).
Devices without separate bypass mains input, absorb energy from the mains. In devices with separate
bypass mains input, energy is drawn from the separate bypass mains.
Bypass Mode Operation can be chosen through the Commands Menu.
If this mode is not chosen by the user, UPS transfers the load automatically to the mains in order to
protect them during abnormal conditions (the inverter is disabled).
While UPS operates
in Online Operation, UPS switches to bypass automatically (in case the mains
voltage and frequency is within the limits of bypass) in the following conditions;
During the start-up
Bypass Priority
Inverter Fault
Prolonged Overload
High Heatsink Temperature
After these conditions are eliminated, the UPS automatically returns to inverter.
UPS switches to another mode in case the mains voltage or frequency go beyond the Bypass limits.
UPS returns to Bypass Operation when the mains returns to the limits.
Bypass Operation Voltage Range
The mains voltage is required to be in certain range for Bypass Operation. Voltage tolerance is set
10% of the output voltage in the factory. For instance; if the output voltage is 220V, the tolerance
range of bypass voltage would be 198V – 242V. In case the input voltage decreases below 198V or
increases above 242V; if UPS runs in Bypass Operation UPS, then switches to Online Operation; if UPS
Bypass
Operation
mode
does
not
provide
perfect
stability
in
frequency/waveform/rms value
of the output voltage like in Online Operation. Thus, the use of this mode should be
carefully
executed according to the level of protection required by the application.
Bypass Operation mode does not provide electronic short circuit protection as
provides in
Online Operation. If a short circuit occurs on the output during this operation, the
thermal/magnetic protection will act and all loads will be deenergized.
Prolonged overloads in Bypass Operation may cause the thermal/magnetic
protection act. In
this case, all loads will be deenergized.
Summary of Contents for ETR EVO Series
Page 16: ...ETR EVO UPS User Manual Ver 1 0 Page 11 10 15kVA 3Ph Input 3Ph Output Terminal Connections...
Page 17: ...ETR EVO UPS User Manual Ver 1 0 Page 12 20 30kVA 3Ph Input 3Ph Output Terminal Connections...
Page 18: ...ETR EVO UPS User Manual Ver 1 0 Page 13 40 60kVA 3Ph Input 3Ph Output Terminal Connections...
Page 19: ...ETR EVO UPS User Manual Ver 1 0 Page 14 80kVA 3Ph Input 3Ph Output Terminal Connections...
Page 20: ...ETR EVO UPS User Manual Ver 1 0 Page 15 100kVA 3Ph Input 3Ph Output Terminal Connections...
Page 21: ...ETR EVO UPS User Manual Ver 1 0 Page 16 120kVA 3Ph Input 3Ph Output Terminal Connections...
Page 22: ...ETR EVO UPS User Manual Ver 1 0 Page 17 160kVA 3Ph Input 3Ph Output Terminal Connections...
Page 23: ...ETR EVO UPS User Manual Ver 1 0 Page 18 200kVA 3Ph Input 3Ph Output Terminal Connections...
Page 36: ...ETR EVO UPS User Manual Ver 1 0 Page 31...
Page 71: ...ETR EVO UPS User Manual Ver 1 0 Page 66 40 200kVA Standard UPS 40 200kVA UPS with Split Bypass...