ETR EVO UPS User Manual (Ver. 1.0)
Page 28
5. MODES OF OPERATION
Uninterruptible Power Supplies (UPS) have an important function in the protection of the critical and
sensitive loads from the irregular mains electricity conditions and they are used to supply
uninterruptible energy to these loads. In such irregular mains electricity conditions, the user can
provide an artificial energy supply to the equipment present in the office or at home by using an UPS.
ETR EVO UPS during Inverter operation provides stable pure sine wave. This pure sine wave is not
affected from the input voltage fluctuations. This helps to extend the life time of your sensible loads.
Power factor of the current consumed from the mains is nearly one. You do not have any problem
on generator or isolation transformer applications. The reactive energy consumption decreases.
During the mains failure, the energy needed for the load is provided by the battery in UPS (or in
external battery cabinet/s). These batteries are charged by an intelligent battery charging circuit
during the mains within the limits. Batteries are lead acid battery (VRLA) and do not require any
maintenance until the end of their life time.
In case of longer overload or inverter failure situation, UPS transfers the load to Bypass line, and load
is supplied from the mains. When the condition turns back to normal, UPS shall continue to supply
the load through inverter.
UPS control and management is done by Digital Signal Processor (DSP) which is 200 times faster than
standard microprocessors. This helps to make your UPS smarter. DSP uses all the sources on optimum
conditions, observes the failure conditions, and communicates with your computer system.
UPS can be operated in one of the following operational modes depending on the condition of mains,
battery, bypass, UPS and/or user preference.
You may see the block diagram of UPS in
Appendix-4 Description of UPS and Block Diagram
Summary of Contents for ETR EVO Series
Page 16: ...ETR EVO UPS User Manual Ver 1 0 Page 11 10 15kVA 3Ph Input 3Ph Output Terminal Connections...
Page 17: ...ETR EVO UPS User Manual Ver 1 0 Page 12 20 30kVA 3Ph Input 3Ph Output Terminal Connections...
Page 18: ...ETR EVO UPS User Manual Ver 1 0 Page 13 40 60kVA 3Ph Input 3Ph Output Terminal Connections...
Page 19: ...ETR EVO UPS User Manual Ver 1 0 Page 14 80kVA 3Ph Input 3Ph Output Terminal Connections...
Page 20: ...ETR EVO UPS User Manual Ver 1 0 Page 15 100kVA 3Ph Input 3Ph Output Terminal Connections...
Page 21: ...ETR EVO UPS User Manual Ver 1 0 Page 16 120kVA 3Ph Input 3Ph Output Terminal Connections...
Page 22: ...ETR EVO UPS User Manual Ver 1 0 Page 17 160kVA 3Ph Input 3Ph Output Terminal Connections...
Page 23: ...ETR EVO UPS User Manual Ver 1 0 Page 18 200kVA 3Ph Input 3Ph Output Terminal Connections...
Page 36: ...ETR EVO UPS User Manual Ver 1 0 Page 31...
Page 71: ...ETR EVO UPS User Manual Ver 1 0 Page 66 40 200kVA Standard UPS 40 200kVA UPS with Split Bypass...