ETR EVO UPS User Manual (Ver. 1.0)
Page 21
4.2.1.5. Output Connection
Please add three-pole circuit breaker (equivalent to UPS output breaker) to distribution panel where
the loads are to be connected. Connect the phase cable to Output L1-L2-L3 terminal and the neutral
cable to Output N terminal. Neutral connection should be done directly.
Danger of explosion and fire if the batteries of the wrong type are used.
The batteries must be charged min. 10 hours before first-use.
Battery fast fuses should be replaced with fuses of the same type and rating.
To enable the short circuit protection feature of the UPS, each load shall be supplied
through
a separate circuit breaker chosen according to the load current. This may provide
quick
disconnection of the short circuited load and maintain operation continuity of the
other
loads. To obtain maximum protection, the rating of each individual load circuit
breaker shall
have the minimum value, which is enough to carry the full load current continuously.
Make sure that all circuit breakers are at “0” position before starting with the
installation.
Each load should be supplied through separate circuit breaker and the cable cross
section
should be chosen according to the load current value.
Make sure that the UPS is not overloaded to provide a higher quality supply to the
loads.
Summary of Contents for ETR EVO Series
Page 16: ...ETR EVO UPS User Manual Ver 1 0 Page 11 10 15kVA 3Ph Input 3Ph Output Terminal Connections...
Page 17: ...ETR EVO UPS User Manual Ver 1 0 Page 12 20 30kVA 3Ph Input 3Ph Output Terminal Connections...
Page 18: ...ETR EVO UPS User Manual Ver 1 0 Page 13 40 60kVA 3Ph Input 3Ph Output Terminal Connections...
Page 19: ...ETR EVO UPS User Manual Ver 1 0 Page 14 80kVA 3Ph Input 3Ph Output Terminal Connections...
Page 20: ...ETR EVO UPS User Manual Ver 1 0 Page 15 100kVA 3Ph Input 3Ph Output Terminal Connections...
Page 21: ...ETR EVO UPS User Manual Ver 1 0 Page 16 120kVA 3Ph Input 3Ph Output Terminal Connections...
Page 22: ...ETR EVO UPS User Manual Ver 1 0 Page 17 160kVA 3Ph Input 3Ph Output Terminal Connections...
Page 23: ...ETR EVO UPS User Manual Ver 1 0 Page 18 200kVA 3Ph Input 3Ph Output Terminal Connections...
Page 36: ...ETR EVO UPS User Manual Ver 1 0 Page 31...
Page 71: ...ETR EVO UPS User Manual Ver 1 0 Page 66 40 200kVA Standard UPS 40 200kVA UPS with Split Bypass...