ETR EVO UPS User Manual (Ver. 1.0)
Page 4
3. REQUIREMENT
3.1. Transportation
3.2. Placement
This product meets the safety requirements for devices to be operated in restricted access locations
according to EN 62040-1 safety standard, which states that the owner should guarantee the
following:
Access to the equipment can only be gained by service person or by user who have been
instructed about the reasons for the restrictions applied to the location and about any precautions
that shall be taken,
Access is through the use of a tool or lock and key, or other means of security and is controlled by
the authority responsible for the location.
UPS is not designed for outdoor application.
The equipment and the batteries should not be exposed to direct sunlight or placed near to a heat
source.
Recommended operating temperature and humidity values are listed on the
section. To provide the required enviromental condition, it might be needed to
climate the room.
Avoid dusty environments or areas where dust of conductive or corrosive materials is present.
The connection and the circuit breakers are at the front of UPS. Leave at least 50 cm at the front
of the UPS for maintenance.
Air outlets of the UPS are on front, rear and top sides. Leave at least 50 cm at the front side, rear
and top side for maintenance and ventilation.
Even though the operating temperature of the UPS and batteries are between 0-40 °C, It is
suggested to provide an environment temperature between 20-25°C to get maximum
performance from the UPS and batteries.
Adviced
Environmental humidity condition is between 20% 80% (non-condensing).
The UPS must be placed and stand in a vertical position throughout the
transportation.
Use suitable equipment to remove the UPS from the pallet.
The equipment shall be packed properly during transportation. Therefore it is
recommended
to keep the original package for feature need.
All packing material must be recycled in compliance with the laws in force in the
country
where the system is installed.
Summary of Contents for ETR EVO Series
Page 16: ...ETR EVO UPS User Manual Ver 1 0 Page 11 10 15kVA 3Ph Input 3Ph Output Terminal Connections...
Page 17: ...ETR EVO UPS User Manual Ver 1 0 Page 12 20 30kVA 3Ph Input 3Ph Output Terminal Connections...
Page 18: ...ETR EVO UPS User Manual Ver 1 0 Page 13 40 60kVA 3Ph Input 3Ph Output Terminal Connections...
Page 19: ...ETR EVO UPS User Manual Ver 1 0 Page 14 80kVA 3Ph Input 3Ph Output Terminal Connections...
Page 20: ...ETR EVO UPS User Manual Ver 1 0 Page 15 100kVA 3Ph Input 3Ph Output Terminal Connections...
Page 21: ...ETR EVO UPS User Manual Ver 1 0 Page 16 120kVA 3Ph Input 3Ph Output Terminal Connections...
Page 22: ...ETR EVO UPS User Manual Ver 1 0 Page 17 160kVA 3Ph Input 3Ph Output Terminal Connections...
Page 23: ...ETR EVO UPS User Manual Ver 1 0 Page 18 200kVA 3Ph Input 3Ph Output Terminal Connections...
Page 36: ...ETR EVO UPS User Manual Ver 1 0 Page 31...
Page 71: ...ETR EVO UPS User Manual Ver 1 0 Page 66 40 200kVA Standard UPS 40 200kVA UPS with Split Bypass...