7.2
Supported DeviceNet Objects compliant with
Semi Guidelines
The PGE500 supports DeviceNet objects, attributes and ser-
vices required for S-Analog Sensor Object Subclass 2, Heat
Transfer Vacuum Gauge.
Class
Object
30 hex
S-Device Supervisor
31 hex
S-Analog Sensor
34 hex
S-Gas Calibration
35 hex
Trip Point
7.3
Other supported DeviceNet Objects
The PGE500 supports the Discrete Output Object, Class 9, get
attribute 3 Value only. Two instances are supported indicating
the state of the Trip Points.
7.4
Configuring the DeviceNet switches
•
Turn off power to the PGE500 by disconnecting the 5-pin
DeviceNet Micro Connector from the network.
•
Set the MAC ID Switches (Node Address Switches) to the
correct address (0-63). Default is 63.
•
Set the data Rate switch to the network baud rate. Default is
125KBaud.
•
Turn on power to the PGE500 by reconnecting the 5-pin
DeviceNet Micro Connector from the network.