Id
Parameter
Parameter
Description
Range
Default
t0
Central heating
ignitions timer
The boiler has an electronic timer, which prevents the burner from igniting too
often in central heating mode
0 - 600
seconds
18
t1
Central heating
ramp timer
In the ignition phase, the boiler performs an ignition ramp in order to arrive at the
maximum power set
0 - 840
seconds
65
t2
CH ignition delay
from TA and CR
request
The boiler is set to switch-on immediately after a request. In the case of particular
systems (e.g. area systems with motorised thermostatic valves etc.) it may be nec-
essary to delay ignition.
0 - 600
seconds
0
t3
Display lighting
Establishes the display lighting mode.
0 Automatic:
the display lights up during use and dims after 15 seconds of inactivity.
In the event of an anomaly the display flashes.
1 Off:
the display is always lit with low intensity
2 On:
the display is always lit with high intensity.
0 - 2
0
t4
Display
Establishes what indicators 17 and 21 display (Fig. 16).
0
Indicator 17: displays the DHW setting;
Indicator 21: in winter mode it displays the set CH setting, while the indicator is
switched off in summer mode
1
Indicator 17: it is switched off in the presence of a request. Without any request
the indicator shows the DHW setting.
Indicator 21: in the presence of a request, it shows the instant flow temperature
of the boiler. Without any request in summer mode, the indicator is off. In winter
mode it shows the set CH setting.
0 - 1
1