• Technical characteristics
Case
Dimension (w x h x d)
71,2 x 90 x 65mm
Connections
Degree of protection
Front face IP54, Terminals IP20
Weight:
MKD4R63FC001
250 gr.
MKD4R63DT - MKD4R63MT
MKD4R125FC001
270 gr.
MKD4R125DT - MKD4R125MT
Display
Type
:
Backlighted LCD display
Auxiliary supply
Value Uaux ac:
230V ± 15%
Measurement
Three-phase 3 and 4-wire network
Voltage (TRMS)
Direct measurement
Three-phase rated voltage Un:
3x230V~ / 3x400V~ ± 15%
Power consumption voltage circuit:
Max. 1,5VA three-phase
Voltage accuracy class:
0,5
Current (TRMS)
Direct measurement
MKD4R63FC001
I
min
0,5A -
I
n
10A -
I
max
63A
MKD4R63DT - MKD4R125DT
MKD4R125FC001
I
min
1A -
I
n
20A -
I
max
125A
MKD4R125DT - MKD4R125DT
Curren accuracy class:
1
Short-time overcurrent
(IEC/EN 62053-21, IEC/EN 62053-23):
30 I
max
/ 10ms
Frequency
Rated frequency
F
n
50Hz; 60Hz
Permitted variation
45...65 Hz
Energies
Active energy accuracy class:
Reactive energy accuracy class:
1 (EN/IEC 62053-21)
2 (EN/IEC 62053-23)
I = 1 A I = 20 A I
= 125 A
min
n
max
(-20°C ) - (60°C)
CAT III
cl .
U
Only MBus
3x230/3x400Vac ±15%
Wh(E
a
):1 (IEC/EN 62053-21)
varh(E
rv
):2
)
(IEC/EN 62053-23
MAX
1 x 2,5 mm
2
6,5 / 7 mm
Rigid
1 x 2,5 mm
2
Flexible
1 x 1,5 mm
2
1 x 4 mm
2
2,5mm PH0
Recommended
torque 0,5Nm
max. 0,6Nm
I = 0,5 A I = 10 A I
= 63 A
min
n
max
I
M
MKD4R63DT - MKD4R63MT
AX
1,5...10 mm
2
/ Ø 4,8 mm
1,5...16 mm
2
/ Ø 4,8 mm
16 mm
2
/ Ø 9,3 mm
25 mm
2
/ Ø 9,3 mm
50 mm
2
/ Ø 15,3 mm
70 mm
2
/ Ø 15,3 mm
0000-00-0000
M
MKD4R125DT - MKD4R125MT
AX
16...50 mm
2
/ Ø 6,4...12,4 mm
25...70 mm
2
/ Ø 6,4...12,4 mm
0000-00-0000
MKD4R63DT - MKD4R63MT
MKD4R125DT - MKD4R125MT
350 mm