Should chimney's pipe inner diameter is 100 mm.
•
Chimney flue test should be performed before making connections. If
the chimney connections should be carried out after removal of the
traction problem had this problem in the chimney.
•
The boiler pipe connected to the horizontal flue pipe must not be longer
than 2m. It is recommended to use 45
⁰
elbows in chimney pipes
instead of 90
⁰
bend. (Site selection for boilers should be determined
by the closest point where the chimney.)
•
In case of a re-ignition after prolonged period of time, the smoke paths
and flue congestion must be checked.
•
To avoid turbulence around the chimney flue without any obstructions
(high buildings, trees, etc.) Must be at least 10 m away.
•
The pellets boiler should be mounted as close to the chimney as possible
(chimney connection should be short).
•
Chimney cap should be used to prevent the flow into the chimney flue
repercussions of windy weather and rain.
•
Concrete blocks is affected by temperature changes, concrete flat roof
which is in direct contact with the air must be absolutely isolated.
•
An accurate and sufficient flue system for smoke extraction (a chimney
with natural traction (2 Pa - 8 Pa) that does not backfire in the event
of a power outage.)is necessary.
•
Necessary precautions should be taken to prevent condensate formed in
the chimney from reaching the boiler.
•
Clogging or closing of the flue outlet poses a great danger.
Boilers must be connected to a chimney duct which can move vertically
smoke outside the building or its flue pipe to the highest point of the
building.
Chimney connections, if that would be considered illegal in the first
combustion fumes can cause the wall to infiltrate the processing of
these leaks may leave traces. Leaked smoke and / or flames can cause
burns or fire because it can be very hot.
Summary of Contents for GT-15
Page 1: ...0 2019 PELET KAZANI KULLANMA KILAVUZU PELLET BOILER USERGUIDE Rev No 2019 1 1...
Page 2: ...1...
Page 29: ...28 8 TEMEL PAR ALAR VE BOYUTLAR Model GT 15...
Page 31: ...30 Model GT 25...
Page 33: ...9 BA LANTI EMALARI 9 1 Anakart Model GT 15 GT 25...
Page 74: ...73 8 MAIN PARTS AND DIAMENTIONS Model GT 15...
Page 76: ...75 Model GT 25...
Page 78: ...9 CONNECTION SCHEMAS 9 1 Mainboard Model GT 15 GT 25...
Page 98: ......
Page 99: ......