9.3  User settings (optional)
9.3.1  Set delay for the switching outputs

• [dS1] = time delay for SP1 / FH1� If the system pressure exceeds SP1 or 

if the system pressure enters the acceptable range (window), the output 

changes the switching status when the time dS1 has elapsed�

• [dr1] = time delay for rP1 / FL1� If the system pressure falls below rP1 or 

if the system pressure leaves the acceptable range (window), the output 

changes the switching status when the time dr1 has elapsed�

 

Select [dS1] or [dr1] and set the value between 0 and 5000 ms in steps 

of 2 ms (at 0 the time delay is not active)�

9.3.2  Set damping for the switching outputs

 

Select [dAP] and set the value�

dAP value = response time between pressure change and change of the 

switching status in milliseconds�

The following fixed values can be set; they define the switching frequency (f 

in Hz) of the output:

dAP 6

10

30

60 100 250 500 1000 2000

f

80

50

16

8

5

2

1

0�5

0�25

9.3.3  Configuration of the display

 

Select [diS] and set the update rate and orientation of the display:

 -[d1]: update of the measured values every 50 ms�

 -[d2]: update of the measured values every 200 ms�

 -[d3]: update of the measured values every 600 ms�

 -[Ph]: display of the pressure peaks remains for a short time (peak 

hold)�

 -[rd1], [rd2], [rd3], [rPh]: display as for d1, d2, d3; rotated by 180°�

 -[OFF]: the display is switched off in the operating mode�

 

Select [cLor] and define the colour of the digital display:

 -[r-on]: display = red if output 1 is switched; display = green if output 1 

is not switched�

 -[G-on]: display = green if output 1 is switched; display = red if output 1 

is not switched�

 -[red]: the colour of the display is red / does not change�

 -[Gren]: the colour of the display is green / does not change�

Summary of Contents for PQ3 Series

Page 1: ...Operating instructions Pressure sensor PQ3xxx UK 80007230 00 06 2019...

Page 2: ...cessories 7 5 2 DIN rail mounting 7 5 3 Panel mounting 8 6 Electrical connection 8 7 Operating and display elements 9 8 Menu 10 8 1 Menu structure 10 8 2 Explanation of the menu 11 9 Parameter setting...

Page 3: ...nts to be provided to the operator and user of the system This documentation must contain all necessary information and safety instructions for the operator the user and if applicable for any service...

Page 4: ...he system pressure differential pressure in compressed air networks and pneumatic systems of machines and plants Avoid static and dynamic overpressure exceeding the specified overload pressure by taki...

Page 5: ...the main connection 2 bar 29 PSI Bursting pressure of the auxiliary connection as opposed to the main connection 12 bar 174 PSI 4 Function 4 1 Output signals The unit displays the current system press...

Page 6: ...ic data and provides the possibility to set the parameters of the unit during operation In addition communication is possible via a point to point connection with a USB adapter cable You will find mor...

Page 7: ...ighten to avoid damage to the thread Maximum tightening torque 2 5 Nm Maximum thread length 7 5mm 5 1 Mounting accessories The following components can be supplied as accessories Order no Mounting set...

Page 8: ...qualified electrician The national and international regulations for the installation of electrical equipment must be adhered to Voltage supply to EN 50178 SELV PELV Disconnect power Connect the unit...

Page 9: ...ted on the label LEDs 5 6 7 not used LED 8 switching status of the output 9 Alphanumeric display 4 digits Display of the current system pressure Indication of the parameters and parameter values 10 Se...

Page 10: ...10 8 Menu 8 1 Menu structure S M M S M M S M M S M S M M S M M S M M M S M M S M S M M M S M M S RUN M M M S M M S M M S M M M S...

Page 11: ...mit values hysteresis function H or window function F either normally open no or normally closed nc Uni Standard unit of measurement for system pressure Lo Minimum value memory for system pressure HI...

Page 12: ...For reducing the value let the display move to the maximum setting value Then the cycle starts again at the minimum setting value 3 Acknowledge parameter value Briefly press Mode Enter The parameter i...

Page 13: ...played here rES Locking unlocking The unit can be locked electronically to prevent unintentional settings Locking is also possible via an IO Link capable parameter setting tool Make sure that the unit...

Page 14: ...sis function Make sure that for ou1 the function Hno or Hnc is set Select SP1 and set the value at which the output switches Select rP1 and set the value at which the output switches off rP1 is always...

Page 15: ...us in milliseconds The following fixed values can be set they define the switching frequency f in Hz of the output dAP 6 10 30 60 100 250 500 1000 2000 f 80 50 16 8 5 2 1 0 5 0 25 9 3 3 Configuration...

Page 16: ...value 0 9 3 5 Differential pressure measurement optimisation of the sensor accuracy During differential pressure measurement the sensor accuracy can be optimised An average system pressure value is e...

Page 17: ...meters Press Mode Enter until the requested parameter is displayed Briefly press Set The unit displays the corresponding parameter value for approx 15 s After another 15 s it returns to the Run mode 1...

Page 18: ...etting User setting SP1 FH1 25 VMR rP1 FL1 23 VMR ou1 Hno coF 0 0 SySP 0 0 dS1 0 dr1 0 dAP 6 diS d2 uni bAr cLor r on the indicated percentage of the final value of the measuring range VMR of the corr...

Page 19: ...19 UK More information at www ifm com...

Reviews: