14
9.2 Set output signals
9.2.1 Set the unit of measurement for system pressure
►
Select [uni] and set the unit of measurement:
[bAr], [kPa], [PSi], [inHg]�
9.2.2 Set the output function
►
Select [ou1] and set the function:
-[Hno] = hysteresis function/normally open,
-[Hnc] = hysteresis function/normally closed,
-[Fno] = window function/normally open,
-[Fnc] = window function/normally closed�
9.2.3 Set the switching limits (hysteresis function)
►
Make sure that for [ou1] the function [Hno] or [Hnc] is set�
►
Select [SP1] and set the value at which the output switches�
►
Select [rP1] and set the value at which the output switches off�
rP1 is always smaller than SP1� The unit only accepts values which are
lower than SP1�
9.2.4 Set the switching limits (window function)
►
Make sure that for [ou1] the function [Fno] or [Fnc] is set�
►
Select [FH1] and set the upper limit of the acceptable range�
►
Select [FL1] and set the lower limit of the acceptable range�
FL1 is always lower than FH1� The unit only accepts values which are lower
than the value for FH1�