NOTE!
Reverse polarity protection not ensured in case of power supply SELV/
PELV on VBB
30
and VBB
0
)
Reverse polarity protection is only ensured in case of supply via the
on-board system (via a battery), if the polarity of the supply is reversed
as a whole (battery connected incorrectly). The basic principle of
the reverse polarity protection is that the upstream fuses are quickly
switched off in case of excessive current�
In case of supply via SELV/PELV, reverse polarity protection is not
ensured�
> The device may be damaged
►
Ensure that the ends of the cables are properly connected to the
connector before connecting the latter to the device, also in case of
supply via the on-board system�
5.2 Connection accessories
You can find more information about the available accessories at:
www�ifm�com
5.3 Connection technology
Observe all notes on connection technology�
►
Note the device label�
►
Use M12 connectors with gold-plated contacts�
►
The M12 connection parts in the device comply with the ingress resistance
requirements of the standard EN 61076-2-101� To adhere to the protection
rating, only cables certified to this standard must be used� The system creator
undertakes to ensure the ingress resistance of cables they have cut to length�
►
Carry out the fitting according to the indications of the cable manufacturer� The
permitted maximum is 10 Nm�
►
During installation, place the M12 connectors vertically so that the coupling nut
will not damage the thread�
► Unused sockets are equipped with protective caps (included). Tightening
torque: 1�3
±0�1
Nm
►
Use a 40-pole connector with individually sealed cores to ensure protection
rating IP 67�