WARNING!
The housing does not meet the requirements concerning protective
earth� Only functional grounding is possible�
> Risk of electrical shock in case of hazardous active voltages in the
control cabinet behind the installation surface�
►
The system creator must separate hazardous active voltages / parts
behind the installation surface from the housing of the device and
its circuits by means of double / reinforced insulation (air creepage
distances, solid insulation).
►
Take single-fault safety into account (e�g� individual core detached
from the terminal ► use cable ties).
►
The responsibility for the electrical protection of the system lies with
the system creator�
When installing the device in a control cabinet, the following requirements
concerning fire protection apply:
If installed according to the information given in 4�3, the device itself complies
with the requirements of the IEC (or DIN EN) 61010-2-201 for a closed device to
prevent fire from spreading�
WARNING!
The damping strip (installation kit) has no flammability rating and thus
presents no fire obstacle�
> Fire protection for the system might not be given or might be
restricted�
►
The system creator has to ensure fire protection depending on the
requirements of his application, if necessary by means of external
precautions�
►
The responsibility for the fire protection of the system lies with the
system creator�
Using the installation kit does not ensure the protection rating of the system
with the installed device� The protection rating depends on the properties
of the control panel / control cabinet (e�g� thickness, material, surface
characteristics, torsional stiffness).