Process and dialogue module ecomatDisplay CR1058, CR1059
11
WARNING!
The housing does not meet the requirements concerning protective
earth� It can only be connected to functional ground�
> Electric shock possible in case of dangerous active voltages in the
control cabinet behind the installation level�
►
The system creator has to separate dangerous active voltages /
parts behind the installation level from the device housing and its
circuits by means of double / reinforced insulation (air/creepage
distances, solid insulation).
►
Consider single error reliability (e�g� individual core detached from
terminal ► Use cable tie).
►
The responsibility for the electrical protection of the system is with
the system creator�
When installing the device in a control cabinet, the following requirements
concerning fire protection apply:
When mounted in accordance with the information in chapter 4�3 the device itself
meets the requirements of the IEC (or DIN EN) 61010-2-201 concerning a closed
device with regard to protection against the spreading of fire�
WARNING!
The damping strip (installation kit) has no flammability rating and thus
presents no fire obstacle�
> Fire protection for the system may not be given or may be
restricted�
►
The system generator has to ensure fire protection depending
on the requirements of his application, if necessary by means of
external precautions�
►
The responsibility for the fire protection of the system lies with the
system creator�
The use of the installation kit does not ensure the protection rating of the
system with the installed device� The protection rating depends on the
properties of control panel / control cabinet (e�g� thickness, material, surface
characteristics, torsional stiffness).