edgeController
22
Only connect the connector when the supply voltage is disconnected. "Hot plugging" is not
permitted.
"Hot plugging" is permitted at the USB type A connector of the connected M12 adapter.
► Use a min. category 5 (Cat 5) cable for the Ethernet connection.
>
5.5
Operating voltage and circuit breakers
61290
► To protect the unit, protect the operating voltage.
Designation
Plug
Operating voltage
Nominal value
fuse
Required triggering
characteristics
VBB
Pin 119
16…32 V DC
3 A
T
fuse
≤ 120 s at max. 6.25 A
Pin 121
3 A
T
fuse
≤ 120 s at max. 6.25 A
Pin 114
15 A
-
Designation
Plug
Operating voltage
Nominal value fuse
Required triggering
characteristics
VBB
Pin 119
20...32 V
▪
3 A (flat vehicle fuse)
▪
2.5 A (5x20 fuse)
T
fuse
≤ 120 s at max. 6.25 A
Pin 121
Pin 114
NOTICE
Circuit breakers are not triggered if the capacity of the supply voltage VBB is not sufficient.
>
Damage to the device
► Ensure that the cable ends are connected correctly to the connector.
► Alternatively supply the unit via a limited energy circuit according to IEC 61010-1 or class 2
according to UL1310.