edgeController
21
5.2
Wiring
61287
Wiring (→ Data sheet)
The terminals may only be supplied with the signals specified in the technical data or on the
device label
Seal the individual cores of unconnected connector pins.
>
5.3
Connection accessories
61288
The unit is delivered without connection accessories.
The following connection accessories are available:
•
E70450, connection cable with connector / M12
•
E70451, connection cable with connector / 2 individual wires
•
EC2099, USB connection cable USB type A socket / M12
You can find more information about the available accessories at:
>
5.4
Connection technology
61289
Observe all notes on connection technology.
► Note the device label.
► Use M12 connectors with gold-plated contacts.
► The M12 connection parts in the device comply with the ingress resistance requirements of the
standard EN 61076-2-101. To adhere to the protection rating, only cables certified to this standard
must be used.
► Carry out the fitting according to the indications of the cable manufacturer. The permitted
maximum is 10 Nm.
► During installation, place the M12 connectors vertically so that the coupling nut will not damage
the thread.
► Unused sockets are equipped with protective caps (included). Tightening torque: 1.3 ±0.1 Nm
► Use 40-pole connectors with individually sealed cores to ensure protection rating IP 65.
► Ensure ingress resistance of self-assembled cables.
► When using self-assembled cables with 40-pole device plug, only contact pins 119,121,
114 (VBB+) and pin 120 (VBB-). All other pins must not be used.
► Always connect the pins 119, 121 and 114 of the VBB+ supply together (connection
cables of the ifm accessories are correspondingly connected).