Mash Bath
I N D U S T R I A L E Q U I P M E N T & C O N T R O L P T Y . L T D .
6 1 - 6 5 M c C l u r e S t . T h o r n b u r y . 3 0 7 1 M e l b o u r n e . A u s t r a l i a
T e l : 6 1 ( 0 ) 3 9 4 9 7 2 5 5 5 F a x : 6 1 ( 0 ) 3 9 4 9 7 2 1 6 6
E m a i l : i e c @ i e c p l . c o m . a u
M A S H B - 2 0 1 9 0 3 1 4 . d o c 1 4 - M a r - 1 9
2 0
INFO2 display
This display contains notes to assist the
operator.
EXIT reverts to program run display.
EDIT PROGRAM display
Program is built from step0 up to final step
or END.
•
On step0, start
o
C is 15
o.
. ‘min’ (time)
is 1 minute and “d/w ml” is zero. For
step0 these are fixed and cannot be
altered.
•
Press “end
o
C” for keypad. Key in
desired end temperature for step0 (pre-
heat is usually to 45
o
).
•
Press “alert” to cycle through the alert
options (0-4). Press HELP for
assistance.
•
Press “stir” to cycle through the
options (NO/YES/INTERMITTENT). For
step0, stir is normally NO.
•
Press below the arrows to cycle
through the cooling options. (WARM
BATH, SLOW COOL, DRAIN ONLY,
DRAIN / REFILL, DRAIN / REFILL
(twice), HOLD COOL). Press HELP
for assistance.
•
Press HELP for useful information.
•
Press EDIT for other program items
that can be edited. Press EXIT to
revert to the SELECTION display.
See next images showing steps 1, 2, 3, 4
and 5 of program #1.
STEP1:
•
The “start
o
C” (45
o
C) is copied from the
“end
o
C” of the previous step. It cannot
be altered.
•
Press “min” and set to 30. Press and
set “end
o
C” to be 45
o
C. This means
the temperature will remain steady at
45
o
C for 30 minutes.
•
Set “alert” at the start of step1 at #1.
When pre-heat is finished, step1 is
entered and alert sounds. Programs
HALTS to load D/W into the pots.
•
Press “d/w ml” to set the initial d/w fill
volume for the pots ( EBC is 200ml).
•
Press ‘stir” to select YES so stirring
occurs when HALT is cancelled by GO.
STEP 1 display