background image

 

9

Application Notes 

  

 

 

 

 

 

Weep Control Fail Safe Wiring. 

When it is winter and your carwash looses power from a storm, you want the system to behave in a manner that 
assumes temperatures are below freezing. Failure to do so could result in serious damage. For this reason, normally 
open solenoid valves are used so that if power is lost, by default your equipment will be protected from freezing 
damage. This means that in warm weather this solenoid must be activated to prevent weeping. For similar fail safe 
reasons, if you loose power only to Zolar, or if the overload protection fuse in Zolar is blown, or if for some reason 
Zolar should fail, then you want the failed state of the unit to default to the same electrical state as if temperatures 
were currently freezing. This means that the N.O. relay contacts should be used to drive the N.O. solenoid valve, and 
it is also the reason the duty cycle graph shows that the relay is Off when it is cold and On when it is warm. 

Weep Control Multiple Probe Sensing. 

The temperature at opposite ends of your carwash may receive sunlight at different parts of the day, causing one side 
to be warmer in the morning and the other to be warmer in the afternoon. It is often difficult to find a single location 
for mounting the Z440TP Temperature Probe that can provide satisfactory safety from freezing under varying 
sunlight conditions. Zolar provides you with the option of using two Z440TP Temperature Probes to solve this 
problem. When configured for using two Temperature Probes for the Weep function, Zolar will use the lower of the 
two temperatures to control the Weep Output duty factor. Zolar will automatically know if the second Temperature 
Probe is to be used with the Weep Output or the Auxiliary Output by how you have configured the Auxiliary Output 
through the front panel Configuration Menu. If the Auxiliary Output is configured to be controlled by either 
temperature or ambient light, then the second Sensor Input will be associated with the Auxiliary Output control. 
However, if you configure the Auxiliary output for control by time of day, then Zolar will use the second Sensor 
Input in the dual Temperature Probe configuration for the Weep Output. (Note: If the Auxiliary Output is configured 
for control by time of day and a 2

nd

 Temperature Probe is not connected, Zolar will ignore the 2

nd

 Sensor Input.) 

Ambient Light Probe Notes. 

The Z440LP Light Probe consists of a light sensor encapsulated in a light diffusing high density polyethylene tube 
encapsulated with silicone sealant. It has fairly omnidirectional sensing characteristics to average light intensity over 
its entire field of view. The light sensor has a filter for blocking visible light but passing infrared light. This allows 
the sensor to easily detect sunlight, which contains a significant amount of infrared light, and ignore light from most 
high powered outdoor lights, such as metal halide, mercury vapor, low pressure sodium and fluorescent lamps, all of 
which emit virtually no infrared light. However, 

incandescent and tungsten halogen lamps do contain a great 

deal of infrared light and should not be used near the Z440LP Light Probe.

This is important in applications 

where the light sensor is being used to control exterior lighting and we do not want these light sources to interfere 
with proper detection of the sunlight intensity. 
 
Typically, ambient light levels are measured in foot-candles (ft.cdl.) or alternatively in Lux. The sun produces about 
8,500 ft.cdl. or 90,000 Lux of light intensity at noon on a clear summer day. Rather than try to remember these 
confusing terms and numbers, Zolar expresses light intensity as a percent of full sunlight brightness. So, a reading of 
33.3% indicates the Light Probe is sensing 1/3 of full sunlight intensity. 
 
Experimental data shows that on a sunny day, the light intensity under the eves on the sunny side of a building is 
about 10% brightness, under the eves on the shady side of a building is about 5% brightness, and inside a self-serve 
carwash bay is also about 5% brightness. There is satisfactory light for washing a car down to light levels in the 
range of 0.5% to 1.0%. The default value set at the factory is 0.7%, but you may adjust this threshold using the 
Menu on the front panel.

 

IDX Inc, 400 W. Cedar St.,  El Dorado, AR 71730   800-643-1109   

[email protected]

   

www.idxinc.com

 

Summary of Contents for Zolar Z440

Page 1: ... cover label near the input power terminals indicates the configuration of the unit Expanded Output Option One each Weep and Auxiliary Outputs are included in the Standard Configuration One each additional Weep and Auxiliary outputs may be added to the Standard Configuration to provide sensing and control for larger carwashes having additional functions or services When the Expanded Output Option ...

Page 2: ... Z440LP Light Probe to Sensor 2 terminals and use the front panel Configuration Menu to configure Aux 1 Output for control by Light The Light Probe will ensure that lights are turned on and off as needed no matter what time of year it is or how thick the clouds are See the Light Probe Application Note for useful information in using this function Time Of Day Control Equipment such as an office air...

Page 3: ...r LEDs are On when their corresponding outputs are On Configuration Menu Just below the dot matrix LED display window is a set of four buttons shown above for navigating the Configuration Menu If the Next or Back keys are pressed the status message is interrupted and the Configuration Menu is entered From the Configuration Menu all time temperature or light threshold set points can be viewed by su...

Page 4: ... to the Start Weep and Full Weep set points as detailed in the diagram on page 2 In the example using Start Weep 34 F and Full Weep 15 F if the sensed temperature is 20 F then we would be 5 from Full Weep out of a total of 19 between Start Weep and Full Weep Since at Start Weep the relay is On 100 of the time then at 20 F the relay would be On 5 19 26 3 of the time during each minute for a period ...

Page 5: ...Blower output will be active low At temperatures below the set point the Foam Blower output will be inactive Once the Foam Blower becomes active the temperature must rise 2 F above the set point before the output will switch to inactive 2 hysteresis The Yes and No keys will modify the set point and the Next key will save the values and advance to the menu to the alarm parameters TEMP 1 ALARM LOW F...

Page 6: ...anufacturers on request Autodialer Interface The Zolar Autodialer Enable output is an open collector NPN transistor that sinks current to Common when activated in an alarm situation Most all autodialers on the market will work with this type of output as it is compatible with a N O relay or switch contact IDX recommends one of the two autodialers below or their successor models The manuals for the...

Page 7: ...ng RED to Sensor BLK to Reference SHLD To Shield Z440LP For Bay Lighting Z440TP For Weep Tunnel Z440TP For Slab Heater Z440TP For Weep Bays Contactor To Bay Lights Solenoid To N O Tunnel Weep Valve Solenoid To N O Bay Weep Valve Contactor To Slab Heater Pump 120VAC Com Hot 24 VAC Common Com ...

Page 8: ...olar detects the Dual Temp Weep configuration automatically when you install two Temperature Probes but configure Aux 1 for control by Time rather than by the attached sensor Zolar then automatically assigns the purpose of the second Temperature Probe to that of Dual Temp Weep 3 Zolar automatically detects the presence or absence of a Temperature Probe When a Temperature Probe is not installed for...

Page 9: ...control by time of day then Zolar will use the second Sensor Input in the dual Temperature Probe configuration for the Weep Output Note If the Auxiliary Output is configured for control by time of day and a 2nd Temperature Probe is not connected Zolar will ignore the 2nd Sensor Input Ambient Light Probe Notes The Z440LP Light Probe consists of a light sensor encapsulated in a light diffusing high ...

Reviews: