background image

 

5

 
 

¾

 

If 

LIGHT

  is selected, the next prompt displays a light intensity set point: 

 

LIGHT TRIP:  0.7% 

The Light Probe is connected to the Sensor #2 input and is calibrated to produce a reading of 100% in direct 
sunlight on a clear summer day at mid latitudes. There is generally sufficient light to wash cars down to about 
0.5% of full sunlight intensity. See the application note later in this document for more lighting information. 
When light levels fall below the Light Trip value, the Aux #1 Output relay will be energized. About 100% 
hysteresis is provided on this Light Trip value to prevent the Aux #1 Output relay from being energized and 
de-energized as moving clouds and other factors vary near sunrise and sunset. You can change the temperature 
trip set point by using the 

+/Yes

 and 

-/No

 keys. The 

Next

  key will save the new value and advance the menu 

to the next item. 

 

 

¾

 

If 

TIME

 is selected, the next two prompts display the time at which Zolar will energize the Aux #1 relay. 

 

ON TIME:   '08:00  

(note the PM indicator just before the numerical digits)

 

OFF TIME:  06:00 

Times can span midnight.  For example, if you wish to have lights come on at 8:00 PM and go off at 6:00 AM, 
set On Time and Off Times as shown in the example above. The 

+/Yes

 and 

-/No

 keys will modify this time 

set point if desired and the 

Next

  key will save the values and advance to the menu to the next parameter. 

 
 
After the Weep and Aux outputs are configured, Zolar presents information for the Foam Blower output set point. 
 

FOAM BLOWER TEMP: °F 34 

 
The Foam Blower output is controlled by the lower of temperature sensor #1 or temperature sensor #3 (if installed). At 
temperatures above the set point, the Foam Blower output will be active low.  At temperatures below the set point, the 
Foam Blower output will be inactive.  Once the Foam Blower becomes active, the temperature must rise 2°F above the 
set point before the output will switch to inactive (2° hysteresis). The 

+/Yes

 and 

-/No

 keys will modify the set point  

and the 

Next 

 key will save the values and advance to the menu to the alarm parameters. 

 
 

TEMP #1 ALARM LOW: °F 55 
 

The last set of parameters presented in the Configuration Menu is for Zolar’s Auto Dialer Alarm capability, which may 
be triggered by either a temperature extreme or a power outage. If the power fails for any reason, the Auto Dialer will 
be triggered as soon as power is restored. Zolar will only prompt you for Alarm set points for those Sensor Inputs 
having attached Temperature Probes. Since Sensors #1 and #3 are each associated with a Weep Output they will trigger 
an Alarm for a low temperature only. Since Sensors #2 and #4 can be used to sense temperatures that are too low, or too 
high, they can trigger an Alarm Output if the temperature gets either too cold or too hot.  This output is designed to be 
used with an Auto Dialer to provide a phone call to an off-site location but could also provide some local alarm 
annunciation if desired. Each temperature set point can be individually adjusted using the 

+/Yes

 and 

-/No

 keys. 

 
To avoid repeated “nuisance” calls for the same problem, once triggered, the alarm output will not re-trigger until all 
trigger sources have maintained a clear state for at least one continuous hour. As there are no more parameters to 
configure, the 

Next 

 key will now return to the Status display. 

 

LOWEST TEMPERATURE: F 12.5 RESET? Y/N 
 

Zolar will keep track of the lowest temperature recorded since last time the value was reset. A Yes response to the 
prompt above would reset the lowest temperature to the current temperature. 

Summary of Contents for Zolar Z440

Page 1: ... cover label near the input power terminals indicates the configuration of the unit Expanded Output Option One each Weep and Auxiliary Outputs are included in the Standard Configuration One each additional Weep and Auxiliary outputs may be added to the Standard Configuration to provide sensing and control for larger carwashes having additional functions or services When the Expanded Output Option ...

Page 2: ... Z440LP Light Probe to Sensor 2 terminals and use the front panel Configuration Menu to configure Aux 1 Output for control by Light The Light Probe will ensure that lights are turned on and off as needed no matter what time of year it is or how thick the clouds are See the Light Probe Application Note for useful information in using this function Time Of Day Control Equipment such as an office air...

Page 3: ...r LEDs are On when their corresponding outputs are On Configuration Menu Just below the dot matrix LED display window is a set of four buttons shown above for navigating the Configuration Menu If the Next or Back keys are pressed the status message is interrupted and the Configuration Menu is entered From the Configuration Menu all time temperature or light threshold set points can be viewed by su...

Page 4: ... to the Start Weep and Full Weep set points as detailed in the diagram on page 2 In the example using Start Weep 34 F and Full Weep 15 F if the sensed temperature is 20 F then we would be 5 from Full Weep out of a total of 19 between Start Weep and Full Weep Since at Start Weep the relay is On 100 of the time then at 20 F the relay would be On 5 19 26 3 of the time during each minute for a period ...

Page 5: ...Blower output will be active low At temperatures below the set point the Foam Blower output will be inactive Once the Foam Blower becomes active the temperature must rise 2 F above the set point before the output will switch to inactive 2 hysteresis The Yes and No keys will modify the set point and the Next key will save the values and advance to the menu to the alarm parameters TEMP 1 ALARM LOW F...

Page 6: ...anufacturers on request Autodialer Interface The Zolar Autodialer Enable output is an open collector NPN transistor that sinks current to Common when activated in an alarm situation Most all autodialers on the market will work with this type of output as it is compatible with a N O relay or switch contact IDX recommends one of the two autodialers below or their successor models The manuals for the...

Page 7: ...ng RED to Sensor BLK to Reference SHLD To Shield Z440LP For Bay Lighting Z440TP For Weep Tunnel Z440TP For Slab Heater Z440TP For Weep Bays Contactor To Bay Lights Solenoid To N O Tunnel Weep Valve Solenoid To N O Bay Weep Valve Contactor To Slab Heater Pump 120VAC Com Hot 24 VAC Common Com ...

Page 8: ...olar detects the Dual Temp Weep configuration automatically when you install two Temperature Probes but configure Aux 1 for control by Time rather than by the attached sensor Zolar then automatically assigns the purpose of the second Temperature Probe to that of Dual Temp Weep 3 Zolar automatically detects the presence or absence of a Temperature Probe When a Temperature Probe is not installed for...

Page 9: ...control by time of day then Zolar will use the second Sensor Input in the dual Temperature Probe configuration for the Weep Output Note If the Auxiliary Output is configured for control by time of day and a 2nd Temperature Probe is not connected Zolar will ignore the 2nd Sensor Input Ambient Light Probe Notes The Z440LP Light Probe consists of a light sensor encapsulated in a light diffusing high ...

Reviews: