TEMP UNITS: 

°

 
This prompt indicates that Zolar is currently configured to display all temperatures degrees Fahrenheit. Use the 

+/Yes

 

or 

-/No

 keys to toggle between the °F and °C format.  Once the desired units are displayed, press the

 Next 

 key to save 

the temperature format and proceed to the next item in Configuration Menu. 
 
 

START WEEP #1:  

°

F  34 

 
This prompt indicates that the Weep #1 Output will start cycling at 34°F.  This output is controlled by the lower of the 
temperatures indicated by Sensor #1 and Sensor #2 (if configured for Dual-Temp Weep). Fail-Safe reasons the Weep 
Output relays are normally energized when it is warm and de-energized when it is cold. Also, for Fail-Safe reasons, we 
recommend using the N.O. relay contacts to drive a N.O. solenoid valve for the weep system. In this manner, if power 
fails or a wire is broken, the weep water will flow and prevent freezing of the high pressure hoses and wands.  The Start 
Weep set point controls the temperature at which "weep cycling" of the output begins. The Start Weep set point can be 
adjusted in one-degree steps by using the 

+/Yes

 and 

-/No

 keys.  The 

Next

 key will save the new value and advance the 

menu to the Full Weep message. 
 
 

FULL WEEP #1:  

°

F 15 

 
This prompt indicates the temperature at which "weep cycling" becomes 100%. At this temperature and below, the 
associated Weep Output relay will always be turned off so that the N.O. solenoid valve will be open providing weep 
water to prevent freezing of the high pressure hoses and wands.  At temperatures between Start Weep and Full Weep, 
the Weep Output relay will energize for only a percentage of each minute in proportion to the proximity of the sensed 
temperature to the Start Weep and Full Weep set points as detailed in the diagram on page 2. In the example using Start 
Weep = 34°F and Full Weep = 15°F, if the sensed temperature is 20°F then we would be 5° from Full Weep out of a 
total of 19° between Start Weep and Full Weep. Since at Start Weep the relay is On 100% of the time, then at 20°F the 
relay would be On 5/19 = 26.3% of the time during each minute, for a period of 16 seconds each minute.  As with the 
Start Weep set point, this set point can be adjusted in one-degree steps by using the 

+/Yes

 and 

-/No

 keys.  The 

Next

 

key will save the new value and advance to the next item in Configuration Menu. 
 

 

AUX #1 TYPE:  TEMP 

 
The equipment connected to the Aux #1 output can be controlled based on time, temperature or ambient light intensity.    
The above message indicates that Zolar is currently configured to control the Aux #1 Output based on having a 
Temperature Probe connected to the Sensor #2 terminals.  If this is not the desired configuration, use the 

+/Yes

 or 

-/No

 

key to select either LIGHT or TIME. 
 

¾

 

If 

TEMP

 is selected, the next prompt displays a temperature set point:  

 

TEMP TRIP:  °F  34   

You can change the temperature trip set point by using the 

+/Yes

 and 

-/No

 keys. The 

Next

  key will save the 

new value and advance the menu to the next item. 
 

AUX #1 ON IF COLD  

This prompt indicates that the Aux #1 Output relay will be energized on temperatures below the Temp Trip 
setting This example setting would be useful to control a pump circulate antifreeze solution in pipes embedded 
in a concrete slab. When controlling Aux Outputs by temperature, Zolar uses 2°F of hysteresis to prevent 
indecisive behavior near the set point. In this example Aux #1 Output will turn Off when the temperature rises 
to 36°F.  You can change the setting to On If Hot by using the 

+/Yes

 and 

-/No

 keys. The 

Next

  key will save 

the new value and advance the menu to the next item. 

 

Summary of Contents for Zolar Z440

Page 1: ... cover label near the input power terminals indicates the configuration of the unit Expanded Output Option One each Weep and Auxiliary Outputs are included in the Standard Configuration One each additional Weep and Auxiliary outputs may be added to the Standard Configuration to provide sensing and control for larger carwashes having additional functions or services When the Expanded Output Option ...

Page 2: ... Z440LP Light Probe to Sensor 2 terminals and use the front panel Configuration Menu to configure Aux 1 Output for control by Light The Light Probe will ensure that lights are turned on and off as needed no matter what time of year it is or how thick the clouds are See the Light Probe Application Note for useful information in using this function Time Of Day Control Equipment such as an office air...

Page 3: ...r LEDs are On when their corresponding outputs are On Configuration Menu Just below the dot matrix LED display window is a set of four buttons shown above for navigating the Configuration Menu If the Next or Back keys are pressed the status message is interrupted and the Configuration Menu is entered From the Configuration Menu all time temperature or light threshold set points can be viewed by su...

Page 4: ... to the Start Weep and Full Weep set points as detailed in the diagram on page 2 In the example using Start Weep 34 F and Full Weep 15 F if the sensed temperature is 20 F then we would be 5 from Full Weep out of a total of 19 between Start Weep and Full Weep Since at Start Weep the relay is On 100 of the time then at 20 F the relay would be On 5 19 26 3 of the time during each minute for a period ...

Page 5: ...Blower output will be active low At temperatures below the set point the Foam Blower output will be inactive Once the Foam Blower becomes active the temperature must rise 2 F above the set point before the output will switch to inactive 2 hysteresis The Yes and No keys will modify the set point and the Next key will save the values and advance to the menu to the alarm parameters TEMP 1 ALARM LOW F...

Page 6: ...anufacturers on request Autodialer Interface The Zolar Autodialer Enable output is an open collector NPN transistor that sinks current to Common when activated in an alarm situation Most all autodialers on the market will work with this type of output as it is compatible with a N O relay or switch contact IDX recommends one of the two autodialers below or their successor models The manuals for the...

Page 7: ...ng RED to Sensor BLK to Reference SHLD To Shield Z440LP For Bay Lighting Z440TP For Weep Tunnel Z440TP For Slab Heater Z440TP For Weep Bays Contactor To Bay Lights Solenoid To N O Tunnel Weep Valve Solenoid To N O Bay Weep Valve Contactor To Slab Heater Pump 120VAC Com Hot 24 VAC Common Com ...

Page 8: ...olar detects the Dual Temp Weep configuration automatically when you install two Temperature Probes but configure Aux 1 for control by Time rather than by the attached sensor Zolar then automatically assigns the purpose of the second Temperature Probe to that of Dual Temp Weep 3 Zolar automatically detects the presence or absence of a Temperature Probe When a Temperature Probe is not installed for...

Page 9: ...control by time of day then Zolar will use the second Sensor Input in the dual Temperature Probe configuration for the Weep Output Note If the Auxiliary Output is configured for control by time of day and a 2nd Temperature Probe is not connected Zolar will ignore the 2nd Sensor Input Ambient Light Probe Notes The Z440LP Light Probe consists of a light sensor encapsulated in a light diffusing high ...

Reviews: