5. General description
Installation instructions AERO ILM
26
640
9
80
8
15
100
810
100
7
85
9
80
640
785
980
100
100
810
815
980
Installation
To facilitate accessibility the outlet opening on the right-hand side should be given preference!
The dimensions speci
fi
ed are clear dimensions. Ensure that the wall opening is 50 mm larger
around the wall insulation.
5.9. Corner installation
Optimum results are achieved if the heat pump is installed in a corner! The wall openings can be implemented
by the building contractor. The wall openings must be insulated with closed porous insulating material (density
50 mm).
5.9.1. Preparation on the construction side - clearance dimensions
A plane and
fi
rm assembly space must be selected. After positioning the heat pump it has to be leveled.
Adjustable feet under the heat pump are provided for this purpose.
Outlet opening to the right
Outlet opening to the left
When using a light shaft this must be at least as wide as the wall opening. The depth must be at
least 400 mm.
N
OTE: Clear dimensions. Increase
the Wall opening according the
insulation.