Technical data
Heatpump type
unit
AERO ILM 2-7
AERO ILM 4-13
Maximum heatpump flow temperature
⁵
°C
62
60
Nominal flow rate heating water (A7°C/W35°C,
Δ
T=5 K)
m³/h
0.8
1.42
Flow rate heating water (A7°C/W55°C,
Δ
T=8 K)
m³/h
0.42
0.77
Integrated loading pump
Yonos Para 7.0
Stratos Para 25/1-9
Free residual pressure loading pump at nominal flow rate
kPa
49
77
Pressure loss heating side
kPa
15
11
Flow- and return connections heating side
R
1“ AG
1“ AG
Flow domestic hot water heater or HGL-flow
R
1“ AG
1“ AG bzw. 5/4“ AG
Condensate run-off connection
R
35 mm
35 mm
Maximum operating pressure heating side
bar
3
3
Residual pressure at maximum speed ¹
Pa
150
110
Nominal air flow rate (A7°C/W35°C
and nominal Compressor speed)
m³/h
1,250
2,200
diameter flexible air outlet hose (accessory)
mm
560
560
Refrigerant
R410A
R410A
Quantity of refrigerant
2
kg
3.2
6.2
GWP
3
1924
Minimum size of installation room
4
m³
7.3
14.1
Quantity of compressor oil (FV50S)
lt.
0.35
1.9
Quantity of compressors
qty
1
1
1
If the fan speed will be raised, the sound power level raises too
² AERO ILM heat pumps work with the by the Kyoto protocol detected safety refrigerant R410A, with a global warming potential of 2088.
3
According to the 5th IPCC report
4
If the installation room falls below the required minimum size, it must be constructed as a machine room in accordance with EN 378.
⁵
The 62°C refers to the max heat pump flow temperature. The resulting lower hot water temperature must be checked in relation to compliance with the drinking water
regulations.
Electrical data
unit
AERO ILM 2-7
AERO ILM 4-13
Electrical power supply compressor
V/Hz
1~ 230/50
3~ 400/50
Electrical power supply heating element
V/Hz
3~ 400/50 or
1~ 230/50
3~ 400/50
Electrical power supply controller
V/Hz
1~ 230/50
1~ 230/50
Maximum operating (starting) current of compressor
A
15.8
19.0
Maximum power consumption electric heating element
A
8.7
8.7
Fuse of control supply
A
B/Z 13
B/Z 13
Fuse of electrical heating element
A
if 3~ 400/50 B/Z 13
if 1~ 230/50 B/Z 32
B/Z 13
Fuse of main power supply compressor
A
C/K 16
C/K 20
Maximum operating current of fan
A
0.24
0.5
Maximum power consumption fan
W
56
115
Protection class
-
IP 20
IP 20