Technical data
IDEC SmartRelay Manual
319
A.11 Technical data:
FL1D-K2B2, FL1D-K2BM2
(1) Voltage output: If short-circuit protection or overcurrent protection is activated for a
voltage output, the error limit of the other voltage is not ensured.
FL1D-K2B2
FL1D-K2BM2
Power supply
Input voltage
24 V DC
24 V DC
Permissible range
20.4 ... 28.8 V DC
20.4 ... 28.8 V DC
Power consumption
25 ...50 mA
35 ...90 mA
Voltage failure buffering
typ. 5 ms
typ. 5 ms
Power loss at 24 V
0.6 ... 1.2 W
0.9 ... 2.2 W
Electrical isolation
No
No
Reverse polarity protection
Yes
Yes
Ground terminal
for connecting ground
and shielding of the
analog output line.
for connecting ground
and shielding of the
analog output line.
Analog outputs
Number
2
2
Voltage range
0 ... 10 V DC
0 ... 10 V DC
Voltage load
>= 5 k
>= 5 k
Current output
-
0/4 ... 20 mA
Current load
-
<= 250
Resolution
10 bit, normalized to 0 ...
1000
10 bit, normalized to 0 ...
1000
Cycle time for analog output
depending on installation
(typ. 50 ms)
depending on installation
(typ. 50 ms)
Electrical isolation
No
No
Line length (shielded and
twisted)
10 m
10 m
Error limit
Voltage output:
+/- 2.5 % at full scale
Voltage output:
+/- 2.5 % at full scale
Current output:
+/- 3 % at full scale
Short circuit protection
Yes
Yes
Response at short-circuit
(1)
(1)
Overload protection
Yes
Yes
Response at overload
(1)
(1)