Technical data
IDEC SmartRelay Manual
315
Delay time at
• 0 to 1
• 1 to 0
typ. 1.5 ms
<1.0 ms (I3 ... I6)
typ. 1.5 ms
<1.0 ms (I3 ... I6)
typ. 1.5 ms
typ. 1.5 ms
Line length (unshielded)
100 m
100 m
Analog inputs
Number
4 (I1=AI3, I2=AI4,
I7=AI1, I8=AI2)
Range
0 ... 10 V DC
input impedance 72
k
Cycle time for analog value
generation
300 ms
max. Input voltage
28.8 V DC
Line length
(shielded and twisted)
10 m
Error limit
+/- 1.5 % at full scale
Digital outputs
Number
4
4
Output type
Relay outputs
Relay outputs
Electrical isolation
Yes
Yes
Dielectric Strength (between power/
input terminals and output terminals)
2,500 V AC, 1 minute
500 V DC, 1 minute
2,500 V AC, 1 minute
500 V DC, 1 minute
In groups of
1
1
Control of a digital input
Yes
Yes
Continuous current I
th (per terminal)
max. 10 A per relay
max. 5 A per relay
Surge current
max. 30 A
max. 30 A
Incandescent lamp load (25000
switching cycles) at
1000 W
1000 W
Fluorescent tubes with ballast
(25000 switching cycles)
10 x 58 W
10 x 58 W
Fluorescent tubes, conventionally
compensated
(25000 switching cycles)
1 x 58 W
1 x 58 W
Fluorescent tubes, uncompensated
(25000 switching cycles)
10 x 58 W
10 x 58 W
Derating
none; across the entire
temperature range
none; across the entire
temperature range
Short circuit-proof cos 1
Power protection B16,
600A
Power protection B16,
600A
FL1E-H12RCE
FL1E-B12RCE
FL1B-M08B2R2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]