Technical data
IDEC SmartRelay Manual
311
Notice: For fluorescent lamps with capacitors, the technical data of fluorescent lamp
ballasts must also be considered. If the maximum allowed surge current is exceeded,
fluorescent lamps must be switched with appropriate contactor relays.
Fluorescent tubes, uncompensated
(25000 switching cycles)
10 x 58 W
Derating
none; across the entire temperature range
Short circuit-proof cos 1
Power protection B16, 600A
Short circuit-proof cos 0.5 to 0.7
Power protection B16, 900A
Parallel output circuits for power increase Not permitted
Protection of output relay (if desired)
max. 16 A, characteristic B16
Minimum Switching Load
10 mA, 12 V DC
Initial Contact Resistance
100 m
maximum (at 1A, 24V DC)
Mechanical Life
10,000,000 operations minimum
(no load, 10 Hz)
Electrical Life
100,000 operations minimum (rated
resistive load, 1800 operations / hour)
Switching rate
Mechanical
10 Hz
Ohmic load/lamp load
2 Hz
Inductive load
0.5 Hz
FL1E-H12RCA
FL1E-B12RCA