4.4.28 PI controller
Short description
Proportional-action and integral-action controllers. You can
use both types of controller individually or combined.
Symbol in IDEC
SmartRelay
Wiring
Description
Input A/M
Set the mode of the controller:
1: automatic mode
0: manual mode
Input R
Use the input R to reset the output
AQ. As long as this input is set, the
input A/M is disabled.
Output AQ is set to 0.
Input PV
Analog value: process variable,
influences the output
A/M
R
PV