Technical data
IDEC SmartRelay Manual
309
A.6 Technical data:
FL1E-H12RCA/FL1E-B12RCA
FL1E-H12RCA
FL1E-B12RCA
Power supply
Input voltage
24 V AC/DC
Permissible range
20.4 ... 26.4 V AC
20.4 ... 28.8 V DC
Reverse polarity protection
not applicable for this module
Permissible mains frequency
47 ... 63 Hz
Power consumption
• 24 V AC
• 24 V DC
76 ... 182 mA
40 ... 100 mA
Inrush current
2.28 A at 24 V DC
2.48 A at 24 V AC
Voltage failure buffering
typ. 5 ms
Power loss
• 24 V AC
• 24 V DC
1.8... 4.4 VA
1.0 ... 2.4 W
Backup of the real-time clock at 25
C
typ. 80 hours without battery cartridge
typ. 2 years with battery cartridge
Accuracy of the real-time clock
typ.
2 s / day