Menu Structure for Wiring Harmonic Distortion Testing

Submenu

Display Menu

Display

Measurement

Lt-

% Line Voltage THD

Line Voltage THD

Hi=

Highest Line Voltage THD

Lo=

Lowest Line Voltage THD

A=

Average Line Voltage THD

LC=

Crest Factor

LH-

Line Voltage Harmonics 

h3=

%THD at 3rd Harmonic

h5=...h15=

% THD for each odd numbered
Harmonic through the 15th 
Harmonic

bAL=

Total of the remaining % THD from 
17th Harmonic to 31st Harmonic

nt-

% Neutral Current THD

Neutral Current THD

Hi=

Highest Neutral Current THD

Lo=

Lowest Neutral Current THD

A=

Average Neutral Current THD

nC=

Crest Factor

nH-

Neutral Current Harmonics

h3=

%THD at 3rd Harmonic

h5=Öh15=

Hot Conductor Resistance

bAL=

Total of the remaining % THD from 
17th Harmonic to 31st Harmonic

Frequency Value

Line Frequency

rCL=

Recall Memory

Blinking rCL SureTest is Recording Data
Sto

Recording Completed

% Line Voltage THD Menu

• Menu Heading - “LT-”
• Measurement at Menu Heading - % Line Voltage THD
• Submenu - yes

“HI=” - Highest % THD
“Lo=” - Lowest % THD
“A=” - Average % THD 
“LC=” - Crest factor of the line voltage

The submenu values are the highest, lowest, and average values taken since
the SureTest was plugged in.

Line Voltage Harmonics Menu

• Menu Heading - “LH-”
• Measurement at Menu Heading - None
• Submenu - yes

“h3=” - % THD at 3rd harmonic
“h5=” - % THD at 5th harmonic
“h7=”...”h15” - % THD is given for every odd harmonic to the 15th 
harmonic
“bAL=” - Total of the remaining %THD from the 17th to 31st harmonic

% Neutral Current THD Menu

• Menu Heading - “nt-”
• Measurement at Menu Heading - % Neutral Current THD
• Submenu - yes

“Hi=” - Highest % THD
“Lo=” - Lowest % THD
“A=” - Average % THD 
“nC=” - Crest factor of the neutral current

Neutral Current Harmonics Menu

• Menu Heading - “nC-”
• Measurement at Menu Heading - None
• Submenu - yes

“h3=” - % THD at 3rd harmonic
“h5=” - % THD at 5th harmonic
“h7=”...”h15” - % THD is given for every odd harmonic to the 15th harmonic
“bAL=” - Total of the remaining %THD from the 17th to 31st harmonic

Summary of Contents for SureTest ST-1THD

Page 1: ...nd Ground Conductors Min Max Avg Peak Neutral to Ground Voltage THD in the Line Voltage and Neutral Current THD per Harmonic up to the 31st Harmonic Line Frequency General Operation The SureTest Model...

Page 2: ...ground conductor Specifications Case Construction GE Cycolac plastic molded Operating Range All measurements except voltage drop FG drop FG conductor resistances 80 300 Volts AC 50 60 Hz Voltage drop...

Page 3: ...HD automatically enters into the out let circuit testing programming menu The LED display cycles between the menu heading and the measurement every four seconds Press and hold the display advance butt...

Page 4: ...edicated circuit Menu Heading Gn Measurement at Menu Heading True RMS Voltage Ground to Neutral Submenu yes Hi Highest Ground to Neutral Voltage Lo Lowest Ground to Neutral Voltage A Average Ground to...

Page 5: ...ecall Memory submenu Pressing the display advance button for three seconds when a blinking rCL is shown on the display will store all of the data into memory overwriting any previous data in memory It...

Page 6: ...a Sto Recording Completed Line Voltage THD Menu Menu Heading LT Measurement at Menu Heading Line Voltage THD Submenu yes HI Highest THD Lo Lowest THD A Average THD LC Crest factor of the line voltage...

Page 7: ...nt at Menu Heading None Submenu yes Blinking rCL Allows access to stored values from memory Sto Stores values into memory Testing with the 61 181 Clamp Adapter These tests can only be accessed by usin...

Page 8: ...on the adapter to a ground such as a metal water or gas pipe prior to GFCI testing 61 176 Isolated Ground Adapter This adapter allows the operator to verify that a receptacle is completely iso lated f...

Page 9: ...e voltage drops the problem is most likely in the circuit between the panel and the first receptacle or at the panel If all branches are in high resistance the problem may be in the cir cuit from the...

Page 10: ...or Event recording SureTest Circuit Harmonics Analyzers Warranty limited solely to repair or replacement no warranty of mer chantability fitness for a particular purpose or consequential damages IDEAL...