Menu Structure for Outlet Circuit Testing
Submenu
Display Menu
Display
Measurement
L-
Line Voltage
True RMS Line Voltage
Hi=
Highest Line Voltage
Lo=
Lowest Line Voltage
A=
Average Line Voltage
P=
Peak Line Voltage
15=
Voltage Drop
% Voltage Drop at 15 Ampere Load
20=
% Voltage Drop at 20 Ampere Load
Gn=
Ground-to-Neutral Voltage
TRMS Ground-to-Neutral Voltage
Hi=
Highest Ground-to-Neutral Voltage
Lo=
Lowest Ground-to-Neutral Voltage
A=
Average Ground-to-Neutral Voltage
P=
Peak Ground-to-Neutral Voltage
ELL=
Estimated Load on Circuit
Ld=
Load (Watts)
PF=
Power Factor of Load
rES=
Resistance
rn=
Neutral Conductor Resistance
rH=
Hot Conductor Resistance
rG=
Ground Impedance
GFCI= GFCI Trip time
Countdown
of Trip Time Testing GFCI Time to Trip
rCL=
Recall Memory
Blinking rCL SureTest is Recording Data
Sto
Recording Completed
Outlet Circuit Testing
Unless a wiring error exists, the ST-1THD will show "Out" in the LED dis-
play. This indicates that the unit is calibrating itself prior to testing. After
this calibration is performed, the ST-1THD automatically enters into the out-
let circuit testing programming menu. The LED display cycles between the
menu heading, and the measurement every four seconds. Press and hold
the display advance button for one second to move to the menu. To enter
the submenu, press the display advance button for three seconds. To navi-
gate from measurement to measurement within the submenu, press the dis-
play advance button. While in the submenu, pressing and holding the dis-
play advance button for three seconds brings the unit back to the menu
structure.
1. Insert the ST-1THD into the receptacle
2. The LED display shows “Out” indicating self-calibration of the unit
3. The LED display cycles between “L_”, indicating that True RMS Line
Voltage is being measured, and the Line Voltage measurement every four
seconds.
4. Press and hold the display advance button for three seconds to access
the Line Voltage submenu.
5. The LED display alternates between “Hi”, indicating that the highest line
voltage is being measured, and the measurement every four seconds
6. Press the display advance button for one second to move to the next test
within the Line Voltage submenu.
7. Press and hold the display advance button for three seconds to return to
the main menu.