Line Voltage Menu

• Menu Heading - “L-”
• Measurement at Menu Heading - True RMS Line Voltage
• Submenu - yes

“Hi=” - Highest Line Voltage
“Lo=” - Lowest Line Voltage
“A=” - Average Line Voltage
“P=” - Peak Line Voltage

The submenu values are the highest, lowest, average and peak values taken
since the SureTest was plugged in.

Voltage Drop Menu

• Menu Heading - “Gn-”
• Measurement at Menu Heading - % Voltage Drop under a full 15 Amp

Load

• Submenu - yes

“20=” - Voltage Drop under 20 Amp Load

The test results for the 20 Amp load test are simulated based on an actual
15 Amp load.

Ground-to-Neutral Voltage Menu

Ground-to-neutral voltage results from current flowing in the neutral con-
ductor from other equipment on the circuit.  High ground-to-neutral voltage
indicates that the circuit may be loaded near its capacity or the neutral con-
ductor may be shared or carrying harmonic distortion.  A reading of less
than 2 volts usually indicates a usable outlet.  An excessive ground-to-neu-
tral voltage may result in inconsistent or intermittent equipment performance

This test can also be used to verify a dedicated circuit.  A measurement
greater than 0.1 volts indicates that the receptacle under test is not on a
dedicated circuit.

• Menu Heading - “Gn-”
• Measurement at Menu Heading - True RMS Voltage, Ground-to-Neutral
• Submenu - yes

“Hi=” - Highest Ground-to-Neutral Voltage
“Lo=” - Lowest Ground-to-Neutral Voltage
“A=” - Average Ground-to-Neutral Voltage
“P=” - Peak Ground-to-Neutral Voltage
“ELL=” - Estimated Load on Circuit
“Ld=” - Load (Watts)
“PF=” - Power Factor of Load

The submenu values are the highest, lowest, average and peak values taken
since the SureTest was plugged in.

After the display is advanced to “Ld” in the submenu, it will cycle between
the load and power factor measurements.  Pressing the display button will
not advance the unit through the programming sequence.  After these mea-
surements are taken, the unit must be removed from the receptacle and re-
inserted.

Resistance Menu

• Menu Heading - “rES-”
• Measurement at Menu Heading - None
• Submenu - yes

“rn=” - Resistance of Neutral Conductor 
“rH=” - Resistance of Hot Conductor
“rG=” - Ground Impedance

The St-1THD checks ground impedance by pulsing 15 amperes from hot-to-
ground to ensure that the resistance is less than 1 Ohm.

GFCI Menu

The ST-1D applies 6mA to ground through a fixed resistor to trip the GFCI.
A functional GFCI will disconnect the power.  The reset may be at the outlet
or at the panel.

WARNING

When testing 3-wire outlets, do not proceed with the GFCI test if the
Wiring Indicator lights indicate a “No Ground” condition exists.
Repair the ground circuit first.

Summary of Contents for SureTest ST-1THD

Page 1: ...nd Ground Conductors Min Max Avg Peak Neutral to Ground Voltage THD in the Line Voltage and Neutral Current THD per Harmonic up to the 31st Harmonic Line Frequency General Operation The SureTest Model...

Page 2: ...ground conductor Specifications Case Construction GE Cycolac plastic molded Operating Range All measurements except voltage drop FG drop FG conductor resistances 80 300 Volts AC 50 60 Hz Voltage drop...

Page 3: ...HD automatically enters into the out let circuit testing programming menu The LED display cycles between the menu heading and the measurement every four seconds Press and hold the display advance butt...

Page 4: ...edicated circuit Menu Heading Gn Measurement at Menu Heading True RMS Voltage Ground to Neutral Submenu yes Hi Highest Ground to Neutral Voltage Lo Lowest Ground to Neutral Voltage A Average Ground to...

Page 5: ...ecall Memory submenu Pressing the display advance button for three seconds when a blinking rCL is shown on the display will store all of the data into memory overwriting any previous data in memory It...

Page 6: ...a Sto Recording Completed Line Voltage THD Menu Menu Heading LT Measurement at Menu Heading Line Voltage THD Submenu yes HI Highest THD Lo Lowest THD A Average THD LC Crest factor of the line voltage...

Page 7: ...nt at Menu Heading None Submenu yes Blinking rCL Allows access to stored values from memory Sto Stores values into memory Testing with the 61 181 Clamp Adapter These tests can only be accessed by usin...

Page 8: ...on the adapter to a ground such as a metal water or gas pipe prior to GFCI testing 61 176 Isolated Ground Adapter This adapter allows the operator to verify that a receptacle is completely iso lated f...

Page 9: ...e voltage drops the problem is most likely in the circuit between the panel and the first receptacle or at the panel If all branches are in high resistance the problem may be in the cir cuit from the...

Page 10: ...or Event recording SureTest Circuit Harmonics Analyzers Warranty limited solely to repair or replacement no warranty of mer chantability fitness for a particular purpose or consequential damages IDEAL...