IDEAL SureTest ST-1THD Instructions Manual Download Page 8

16

15

Menu Structure for Current Probe Menu Testing (ST-1THDC Only)

Submenu

Display Menu

Display

Measurement

cA-

Current

Current

Hi=

Highest Current

Lo=

Lowest Current

A=

Average Current

ct-

% Current THD

% Current THD

Hi=

Highest Current THD

Lo=

Lowest Current THD

A=

Average Current THD

P=

Peak Current THD

cH-

Current Harmonics 

h3=

%THD at 3rd Harmonic

H5=...H15=

% THD for each odd numbered 
Harmonic through the 15th 
Harmonic

bAL=

Total of the remaining % THD from 
17th Harmonic to 31st Harmonic

Optional Accessories

#61-175  Ground Continuity Adapter

This adapter allows the operator to verify that a cabinet or equipment chas-
sis has been properly connected to the power system ground.  Plugging
into the #61-175 adapter will isolate the SureTest from the power source
ground.  The LED display of the ST-1THD will read “E-nG”.  If the equip-
ment is properly grounded, then touching the alligator clip from the ground
continuity adapter to the cabinet or equipment chassis should return the cir-
cuit to a Normal condition.  

WARNING

This is a static test and will not confirm the current carrying capacity 

With the ST-1D, this adapter can be used to check the ground impedance of
a cabinet or equipment chasis.  See section 3.4 for test instructions.

This adapter can also be used to test GFCI receptacles on 2-wire circuits.
Connect the ground lead on the adapter to a ground, such as a metal water
or gas pipe, prior to GFCI testing. 

#61-176  Isolated Ground Adapter

This adapter allows the operator to verify that a receptacle is completely iso-
lated from the other grounds between the receptacle and the entry panel.  

WARNING

The receptacle should be tested for proper grounding prior to testing
for ground insulation.

Test the ground impedance of the receptacle and make a note of the results.
See the section on outlet circuit testing for details.  Remove the SureTest
from the receptacle and plug it into the #61-176 adapter.  Clip the ground
wire to the metal outlet, center receptacle screw, or the metal outlet box.
Re-insert the ST-1THD into the receptacle and retest for ground impedance.
Make a note of the result.

If the two resistance readings are the same, then the receptacle is not isolat-
ed.  If the receptacle is isolated, the reading with the #61-176 will be lower.
A reading of half when the adapter is used is common, because a parallel
ground path has been introduced by attaching the ground wire to the
grounding point of the receptacle.

#61-177  Extension Cord

The ST-1THD is supplied with an extension cord to make testing easier on
hard-to-reach outlets.  Replacement extension cords can be purchased from
your authorized IDEAL distributor.

#61-179

CARRYING CASE

The ST-1THD is supplied with a lightweight carrying case to protect the
units and store the instruction sheet and accessories.  Replacement cases
can be purchased from your authorized IDEAL distributor.

Summary of Contents for SureTest ST-1THD

Page 1: ...nd Ground Conductors Min Max Avg Peak Neutral to Ground Voltage THD in the Line Voltage and Neutral Current THD per Harmonic up to the 31st Harmonic Line Frequency General Operation The SureTest Model...

Page 2: ...ground conductor Specifications Case Construction GE Cycolac plastic molded Operating Range All measurements except voltage drop FG drop FG conductor resistances 80 300 Volts AC 50 60 Hz Voltage drop...

Page 3: ...HD automatically enters into the out let circuit testing programming menu The LED display cycles between the menu heading and the measurement every four seconds Press and hold the display advance butt...

Page 4: ...edicated circuit Menu Heading Gn Measurement at Menu Heading True RMS Voltage Ground to Neutral Submenu yes Hi Highest Ground to Neutral Voltage Lo Lowest Ground to Neutral Voltage A Average Ground to...

Page 5: ...ecall Memory submenu Pressing the display advance button for three seconds when a blinking rCL is shown on the display will store all of the data into memory overwriting any previous data in memory It...

Page 6: ...a Sto Recording Completed Line Voltage THD Menu Menu Heading LT Measurement at Menu Heading Line Voltage THD Submenu yes HI Highest THD Lo Lowest THD A Average THD LC Crest factor of the line voltage...

Page 7: ...nt at Menu Heading None Submenu yes Blinking rCL Allows access to stored values from memory Sto Stores values into memory Testing with the 61 181 Clamp Adapter These tests can only be accessed by usin...

Page 8: ...on the adapter to a ground such as a metal water or gas pipe prior to GFCI testing 61 176 Isolated Ground Adapter This adapter allows the operator to verify that a receptacle is completely iso lated f...

Page 9: ...e voltage drops the problem is most likely in the circuit between the panel and the first receptacle or at the panel If all branches are in high resistance the problem may be in the cir cuit from the...

Page 10: ...or Event recording SureTest Circuit Harmonics Analyzers Warranty limited solely to repair or replacement no warranty of mer chantability fitness for a particular purpose or consequential damages IDEAL...

Reviews: