28
Falcon GTE -
Installation & Servicing
SERVICING
1
2
fal5943
55 CLEANING THE FLUEWAY
1.
Close off the fuel supply to the burner.
2.
Ensure that the boiler has been cooled to
ambient temperature.
3.
Isolate the mains supply to the boiler and
burner.
4.
Disconnect the cable and supply pipe to the
burner.
5.
Open the combustion chamber door by
removing the 2 special bolts.
6.
Remove the flue way baffles.
7.
Thoroughly clean the flue ways and baffles.
8.
Remove the rear cleanout covers and
dispose of the debris/soot that may have
accumulated.
9.
Replace the rear cleanout covers after first
inspecting and if necessary replacing the
seal.
10.
Brush out the combustion chamber and
vacuum the soot from beneath the flue ways.
11.
Replace the flue baffles into the flue ways:
4 section models - fit 3 flue baffles, one each
flue
5-8 section models - fit 2 flue baffles only in
the centre and right hand flues.
12.
Check the condition of the combustion
chamber door insulation.
13.
Check the condition of the combustion
chamber door seal.
14.
Close the combustion chamber door and
replace the front panel.
15.
Re-assemble the burner connections.
54 MAINTENANCE
WARNING
The operations described below shall always be
performed with the boiler and the power supply
switched off.
The boiler front panel has to be removed to access the
various devices to be maintained and checked.
1.
Pull the front panel forward at the top.
2.
Lift off the engaging clips.
Cleaning the Casing Material
Use a soapy solution and sponge only. Rinse with
clean water and dry with chamois leather or soft cloth.
fal5943
5
4
fal5936
10
6
6
6
4 section
model only
All models
All models
SER