EXALT PROPANE TO NATURAL GAS CONVERSION INSTRUCTIONS 

 

NOTICE 

 

 

4.

 

Press the CENTER button while the FAN icon is 

highlighted to manually fire the burner and power 

the CH circulator. See Fig. 5. 

 

 

An adequate CH load must be present to dissipate the heat 

generated during the combustion test. If an adequate CH 

load is not available, an indirect water heater can be used to 

dissipate the heat by creating a DHW call which will enable 

the DHW circulator. 

 

5.

 

Press the RIGHT button to adjust the firing rate to 

100% (high fire). Hold down the RIGHT button to 

rapidly increase the firing rate. 

6.

 

If the combustion levels during high fire are outside 

the recommended combustion settings (see Table 

1), adjust the THROTTLE SCREW (see Fig. 6) using a 

flat-blade screwdriver as follows: 

 

 

Counter-clockwise adjustment of the THROTTLE 

SCREW at High Fire (100% firing rate): 

O

decreases and CO

increases 

Clockwise adjustment of the THROTTLE SCREW at 

High Fire (100% firing rate): 

O

increases and CO

decreases 

 

 

7.

 

Once the combustion level is set at high fire, 

manually place the boiler into low fire mode by 

pressing the LEFT button to adjust firing rate down 

to 1% (low fire). 

8.

 

If the combustion level (O

or CO

2

) during low fire is 

outside the recommended combustion settings in 

Table 1 contact Ideal USA Technical Support. 

9.

 

Press the CENTER button while the fan icon is 

highlighted to shutdown the burner. 

10.

 

Press the LEFT or RIGHT button to highlight the 

home screen icon to exit the service mode. 

11.

 

Replace the front panel and put the boiler back 

into operation. 