EXALT PROPANE TO NATURAL GAS CONVERSION INSTRUCTIONS 

 

WARNING 

NOTICE 

1.

 

Preliminary Instructions: 

1.

 

Verify that the venturi replacement kit is correct for 

the model of boiler. See page 1. 

2.

 

Turn off electrical power supply to the boiler. 

3.

 

Close the manual gas shut off valve to the unit. 

4.

 

Remove the front panel of the Exalt. 

For the floor standing model: 

Remove the two securing screws on top of the 

control pod. Rotate the pod upwards. Lift the front 

panel to disengage the keyhole slots and remove 

the panel. 
Re-fit in the reverse order. 

For the wall hung model 

Remove the securing screw holding the bottom of 

the front panel to the chassis. Pull the bottom of 

the front panel out and lift to disengage from the 

top mounting points. 
Re-fit in the reverse order. 

 

5.

 

Using a voltmeter ensure there is no electrical 

power to the boiler by checking for power on the 

boiler’s high voltage terminals L and N. 

 

 

ELECTRICAL SHOCK HAZARD 

Ensure power to the boiler has been disconnected 

prior to servicing the unit. 

 

2.

 

Acoustic Foam 

 

Do not remove any of the acoustic foam from either the air 

inlet or the vent outlet. 

The air inlet does not need to be changed to convert from LP 

to Natural Gas. 

Venturi 

Venturi Interface 

Pipe to Venturi 

Gas Valve 

Air Inlet 

Air Reference Hose 

Fig. 1:  Exalt 110 Gas Train 

Air Reference Hose 

Pipe to Venturi 

Gas Valve 

Air Inlet 

Venturi 

Interface 

Venturi 

Fig. 2:  Exalt 155 Gas Train 

Air Inlet 

Venturi 

Interface 

Venturi 

Air Reference 

Hose 

Pipe to 

Venturi 

Gas Valve 

Fig. 3:  Exalt 199 Gas Train 