EXALT PROPANE TO NATURAL GAS CONVERSION INSTRUCTIONS
!
WARNING
NOTICE
1.
Preliminary Instructions:
1.
Verify that the venturi replacement kit is correct for
the model of boiler. See page 1.
2.
Turn off electrical power supply to the boiler.
3.
Close the manual gas shut off valve to the unit.
4.
Remove the front panel of the Exalt.
For the floor standing model:
Remove the two securing screws on top of the
control pod. Rotate the pod upwards. Lift the front
panel to disengage the keyhole slots and remove
the panel.
Re-fit in the reverse order.
For the wall hung model
Remove the securing screw holding the bottom of
the front panel to the chassis. Pull the bottom of
the front panel out and lift to disengage from the
top mounting points.
Re-fit in the reverse order.
5.
Using a voltmeter ensure there is no electrical
power to the boiler by checking for power on the
boiler’s high voltage terminals L and N.
ELECTRICAL SHOCK HAZARD
Ensure power to the boiler has been disconnected
prior to servicing the unit.
2.
Acoustic Foam
Do not remove any of the acoustic foam from either the air
inlet or the vent outlet.
The air inlet does not need to be changed to convert from LP
to Natural Gas.
Venturi
Venturi Interface
Pipe to Venturi
Gas Valve
Air Inlet
Air Reference Hose
Fig. 1: Exalt 110 Gas Train
Air Reference Hose
Pipe to Venturi
Gas Valve
Air Inlet
Venturi
Interface
Venturi
Fig. 2: Exalt 155 Gas Train
Air Inlet
Venturi
Interface
Venturi
Air Reference
Hose
Pipe to
Venturi
Gas Valve
Fig. 3: Exalt 199 Gas Train