background image

EXALT PROPANE TO NATURAL GAS CONVERSION INSTRUCTIONS 

 

WARNING 

WARNING 

Manual Operation 

 

Released 

CH1 

 

DHW 

Off 

Off 

Off 

CH2 

FAN

 

5.  Combustion Test and Adjustments 

 

Do not check for gas leaks with an open flame. Use a 

bubble test. Failure to test for gas leaks can result in 

substantial property damage, serious injury, or death. 

 

7.

 

Attach the natural gas conversion label to the gas 

valve and the natural gas conversion rating label 

next to the existing rating label. 

8.

 

Enter the natural gas appliance code from the 

propane rating label supplied in the conversion kit: 

1.

 

Press and hold the UP and DOWN buttons 

together see Fig. 4. 

 

Fig. 4: CTRLMax Navigation Control 

2.

 

Enter the installer access code “054” by using 

the LEFT and RIGHT buttons to select a digit and 

the UP and DOWN buttons to change the digit. 

Press the center button to enter the access code. 

3.

 

With the CH/DHW Settings icon highlighted, 

press the center button. 

4.

 

Press the DOWN button to highlight the Boiler 

Settings icon then press the center button. 

5.

 

Scroll down to highlight Appliance Setting then 

press the center button. 

6.

 

Enter the natural gas appliance code from 

the rating label by using the LEFT and RIGHT 

buttons to select a character and the UP and 

DOWN buttons to change the character. Press 

the center button to enter the appliance code. 

 

The installer MUST perform a complete combustion check to 

ensure the following combustion levels are met at high and 

low input firing rates and the burner is operating at optimum 

conditions. 

 

The combustion testing and adjustments must be 

performed by a qualified installer, service agency or 

the gas supplier. All combustion measurements must 

be performed with calibrated equipment to ensure 

proper readings and accuracy. Refer to Table 1 to 

check the combustion is within the acceptable range. 

 

Failure to perform a complete combustion test at both 

high and low input rates may result in incomplete 

combustion and the production of carbon monoxide, 

which can cause severe personal injury, death or 

substantial property damage. 

 

1.

 

Touch simultaneously on the up and down soft 

keys for 3 seconds to access the functions for the 

installer. See Fig. 4. 

2.

 

Enter the installer access code “054” by using the 

LEFT and RIGHT buttons to select a digit and the UP 

and DOWN buttons to change the digit. Press the 

CENTER button to enter the access code. 

3.

 

Press the RIGHT button to highlight the Manual 

Operation icon then press the CENTER button. 

 

Fig. 5: CTRLMax Manual Operation 

WARNING 

NOTICE 

Reviews: