background image

EXALT PROPANE TO NATURAL GAS CONVERSION INSTRUCTIONS 

 

NOTICE 

WARNING 

NOTICE 

WARNING 

3.

 

Removal of Propane Gas Venturi 

1.

 

Remove the silicone tube from the air inlet elbow, 

then remove the air inlet elbow. 

2.

 

Rotate the venturi interface approximately 60° 

clockwise to release the clamping mechanism and 

remove the venturi interface. 

3.

 

Remove the gas valve to venturi pipe by loosening 

the nuts at both ends of the pipe with an adjustable 

wrench. 

 

There are gaskets at both ends of the gas valve to venturi 

pipe. These gaskets must be reinstalled along with the pipe. 

Use care not to damage the gaskets. 

4.

 

Using a 10 mm socket and ratchet, remove the 

three (3) bolts securing the venturi to the fan 

assembly and remove the propane venturi from 

the unit, making sure not to damage the blower 

O-ring gasket. 

 

4.

 

Install the Natural Gas Venturi 

1.

 

Verify the following when aligning the natural gas 

venturi: 

1.

 

The UP arrow on the plastic housing is pointing 

upward. 

2.

 

The threaded connection for the gas piping is in 

the correct orientation for re-fitting the gas pipe. 

 

 

Failure to retain the O-ring gasket between the venturi 

and the blower will cause an improper seal resulting 

in a potential risk of a gas leak.  A gas leak can result in 

substantial property damage, serious injury, or death. 

 

 

Ensure the correct venturi for the model is installed. 

Natural gas venturis have a white identification label 

and LP venturis have a black label. Failure to comply 

will affect input rate and combustion of the boiler 

which can result in substantial property damage, 

serious injury, or death. 

 

 

Do not use adhesive on any gaskets or O-rings during the 

reassembly process. 

2.

 

Using a 10 mm socket and ratchet, reinstall the 

three (3) bolts securing the venturi to the fan 

assembly 

3.

 

Reassemble the gas valve to venturi pipe to the 

gas valve and venturi taking care to ensure that the 

gaskets are seated properly before tightening the 

nut. 

4.

 

Install the venturi interface on the venturi and 

rotate counterclockwise until locked into place. 

5.

 

Install the air inlet elbow then attach the silicone 

tube. 

 

 

Failure to properly install the air inlet elbow and attach 

the silicone tube can affect combustion of the boiler 

which can result in substantial property damage, 

serious injury, or death. 

6.

 

Open the manual gas shut off valve to the unit. 

Before placing the boiler back into operation, test 

all gas connections for leaks and repair if leaks are 

found. 

WARNING 

Reviews: