background image

EXALT PROPANE TO NATURAL GAS CONVERSION INSTRUCTIONS 

 

 

 

 

 

Table 1:  Combustion Settings 

 

 

Natural Gas 110, 155 

Natural Gas 199 

Hi

gh

 Fi

re

 

CO

Range 

9.0 - 10.5% 

8.5 to 10.5% 

CO

Target 

9.5% 

O

Range 

4.85 to 2.15% 

5.75 to 2.15% 

O

Target 

3.95% 

CO Max 

<150ppm @ 9.5% CO₂ 

Lo

w

 Fi

re

 

CO

Range 

9.0 to 10.0% 

8.5 to 10.0% 

CO

Target 

9.5% 

9.0% 

 

Target values are equivalent to High Fire values, ensure 

CO₂ values measured are less than or equal to High Fire 

CO₂ measurements 

O

Range 

4.85 to 3.0% 

5.75 to 3.0% 

O

Target 

3.95% 

4.85% 

 

Target values are equivalent to High Fire values, ensure 

O₂ values measured are higher than or equal to High Fire 

O₂ measurements 

CO Max 

10 ppm 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Throttle Screw 

Fig. 6:  Throttle Screw Location 