40 / 74
00U07352250-A_ EN
AHP60
26/32 kW -
Installation, Use and Maintenance
3.6.3. Current source
The ratings and dimensions of the power cables, electrical protections and line fuses must
comply with the indications of the unit’s wiring diagram and the electrical data of the technical
specifications table (
see paragraph 2.4.1)).
Use a dedicated power line, do not power the appliance via a line to which other users are
connected. Securely fasten the power cables and make sure they do not come into contact with
sharp corners. Use double-insulated cables with copper wires.
The earth connection should be made first during the connection phase and vice versa, it should
be removed last when the unit is disconnected. In the power cable comes loose, make sure that
the active conductors are powered before the earth wire.
A proximity switch with adequate breaking capacity must be installed on the supply line, with
contact separation for all poles. The earth fault circuit breaker must be compatible with the
inverters, we recommend fitting a type B differential circuit breaker, as fitting a different type of
circuit breaker could lead to unwanted tripping.
The following table shows the recommended cable sections for a maximum length of 30 m. In all
cases, depending on the type of installation, the physical location and the length of the cables
(under or over 30 m), the electrical system installer must make the appropriate choice.
The units comply with electromagnetic compatibility specifications, but the electrical installation
designer must still make the appropriate assessments to ensure there is no interference.
DANGER:
Electrical connections must only be carried out by QUALIFIED PERSONNEL, in
compliance with the legislation in force.
Ensure that an adequate earth connection is installed, as inadequate earthing
can cause electrical shocks. The manufacturer cannot be held responsible for
damage caused by ineffective or absence of earthing.
Electrical
power supply
Models
Recommended
cable section
(Max. length 30 m)
Maximal current
load (A)
Recommended tightening
torque:
400V / 3ph + N
26 kW
5 x 6 mm
2
23.3
L1/L2/L3: 3.4 Nm – N/PE: 1 Nm
400V / 3ph + N
32 kW
5 x 6 mm
2
27.1
L1/L2/L3: 3.4 Nm – N/PE: 1 Nm