3.3.2. Installation precautions
We recommend that you carry out a noise nuisance risk study.
This will have to take into account the residual noise without the heat pump, the data of the
machine, the implatation zone, the distance to the measurement point, this list is not exhaustive.
The day and night normative noise level requirements are distinct.
In order to reduce the risks, it is advisable to study the vibration transmissions from the machine
to the building, as well as piping, reverberation,...
3.3.2.1.
Principle of reflection of the noise emitted.
Inner courtyards and closed corners should be avoided as far as possible.
The volume also has an impact, for example a small inner courtyard leads to a greater reflection.
Heat pump on the ground or on a
terrace (free field without obstacle)
Heat pump placed against a wall
shows doubled noise perception
Heat pump placed in a wall angle
shows quadruple noise perception
Heat pump placed in an inner courtyard
shows eight-fold noise perception