![Ideal Heating ECOMOD AHP60 26 kW Installation And Servicing Download Page 16](http://html1.mh-extra.com/html/ideal-heating/ecomod-ahp60-26-kw/ecomod-ahp60-26-kw_installation-and-servicing_3613769016.webp)
16 / 74
00U07352250-A_ EN
AHP60
26/32 kW -
Installation, Use and Maintenance
TECHNICAL CHARACTERISTICS
Measurement
units
AHP 60
26 kW
32 kW
Heating
Heat output (1)
min/nom/max
kW
9.5 / 26.0 /
27.3*
11.9 / 32.1 /
33.9*
Absorbed power (1)
kW
6.44
7.84
C.O.P. (1)
W/W
4.04
4.09
Nom thermal power (2)
kW
25.1*
31.8*
Absorbed power (2)
kW
9.51
12.10
C.O.P. (2)
W/W
2.64
2.64
SCOP (3)
W/W
4.55
4.81
Water flow rate (1)
m
3
/h
4.5
5.5
Useful head (1)
kPa
55
48
Energy efficiency
Water 35°C / 55°C
Class
A++/A+
A++/A+
Compressor
Type
Twin Rotary DC Inverter
Oil (type)
FW65S or equivalent
Number of compressors
1
1
Quantity of oil
L
1.5
1.5
Refrigerating circuits
1
1
Refrigerant
Type
R32
R32
Refrigerant load (4)
kg
4.3
5.1
Quantity of refrigerant in equivalent of CO
2
(4)
t
2.90
3.44
Operating pressure (high/low) in heat pump mode
bar
42.8/1.3
42.8/1.3
Internal
exchanger
Water content
L
1.7
2.1
Internal exchanger type
Plates
2.4. Technical data
2.4.1. Data sheet for standard units
This product is designed to be installed at a maximum altitude of 2000m
(*) with the
Hz maximum
function activated